Osburn OB02401 User Manual

Page 13

Advertising
background image

13


The more extended the insert, the greater the heat transfer to the room. When installed as an
extended insert, the front edge of the air jacket will be installed flush with the fireplace facing.
Otherwise the unit can be moved back as much as 3 3/4" (95 mm) or any position in between.
The position chosen will depend on your own preference for most installations, your current
configuration, the compliance with the preceding installation instructions and compliance with the
building code requirements. To determine the minimum and maximum protrusion of the insert,
refer to table Data for floor protection calculation.

Data for floor protection calculation

MAXIMUM
EXTENDED

A

B

(Note 1)

C

E

AIR JACKET

Smaller

than 6 ft

2

*

Bigger or

= to 6 ft

2

*

INCHES

16"

20"

CAN: 18"
USA: 16"

7"

8 1/2"

Flush with
fireplace
facing

MILLIMETRES

406 mm

508
mm

CAN: 457 mm

USA: 406 mm

178 mm

216 mm

MINIMUM
EXTENDED

A

B

(Note 1)

C

E

AIR JACKET

Smaller

than 6 ft

2

*

Bigger or

= to 6 ft

2

*

INCHES

16"

20"

CAN: 18"
USA: 16"

3 1/4"

12 1/4"

Back from
fireplace
facing 3 3/4"

MILLIMETRES

406 mm

508
mm

CAN: 457 mm

USA: 406 mm

83 mm

311 mm

*Refers to masonry fireplace opening.