0 installation – Osburn OB02401 User Manual

Page 7

Advertising
background image

7

2.0 INSTALLATION


2.1 Safety information

NOTE: THIS APPLIANCE IS NOT RECOMMENDED FOR USE IN A HOME IF AN OCCUPANT HAS

ANY RESPIRATORY OR ANY OTHER RELATED PROBLEMS.

1. It is important to follow the installation and operation instructions. An improperly installed

or operated insert could result in a safety hazard or fire, or damage to the unit, which
would not be covered by the warranty. Contact local building or fire officials about
restrictions and installation requirements in your area. You should be familiar with the
installation and be sure that the work is done in accordance with this manual.

WARNING: DO NOT INSTALL THIS INSERT IN A SLEEPING ROOM.

2. Where lesser clearances are desired, consult your local authority as regulations may vary

regarding the use of clearance reducing devices. Listed wall and floor shields are
available to reduce clearances, and most building codes provide information on materials
which may be used to reduce clearances.

3. Maintain at least the minimum clearances to combustible material as specified in this

manual. Clearances are measured to the nearest part of the insert (i.e. top edge on the
side). Clearances to any combustibles, when measured directly out from the front, must
be a minimum of 48" (1219mm).

4. Maintain at least the minimum floor protection for combustible floor materials as specified

in this manual. Floor protection to the front is to be measured from the fuel loading door
opening.


5. Osburn recommends that you install a listed smoke detector or alarm in your home.

Normal operation of the insert will have no effect on the detector or alarm.


6. The insert is to be connected only to a lined masonry chimney and masonry fireplace

conforming to building codes for use with solid fuel. Do not remove bricks or mortar from
the existing fireplace when installing the insert.

7. Minimum chimney size is 6" (152mm) diameter. Maintain a 15' (4.5m) minimum overall height

measured from the base of the appliance. Chimneys should be inspected to check for
deterioration and to determine if they meet the minimum requirements, and be upgraded if
necessary. The chimney must extend at least 3' (914mm) above the roof and at least 2' (610mm)
above the highest point within an area of 10' (3m) of the chimney.

8. Do not use makeshift compromises during installation, as they could create a safety

hazard and a fire could result.


9. DO NOT CONNECT THIS APPLIANCE TO THE CHIMNEY OR FLUE SERVING

ANOTHER APPLIANCE.

Advertising