Installation instructions, Venting for direct-vent water heater (cont.), Venting – Paloma PHH-32 part 1 User Manual

Page 36

Advertising
background image

36

Venting

INSTALLATION INSTRUCTIONS

Venting for Direct-Vent Water Heater (cont.)

In the Commonwealth of

Massachusetts

The Commonwealth of Massachusetts requires

compliance with regulation 248 CMR 4.00 and 5.00 for

installation of through-the-wall vented gas appliances as

follows:
5.08: Modifications to NFPA–54, Chapter 10
(1) Revise NFPA–54 section 10.5.4.2 by adding a second

exception as follows:

Existing chimneys shall be permitted to have their use

continued when a gas conversion burner is installed,

and shall be equipped with a manual reset device that

will automatically shut off the gas to the burner in the

event of a sustained back-draft.
(2) Revise 10.8.3 by adding the following additional

requirements:

(a) For all side-wall, horizontally vented, gas-fueled

equipment installed in every dwelling, building,

or structure used in whole or part for residential

purposes, including those owned or operated by the

Commonwealth and where the side-wall exhaust vent

termination is less than seven (7) feet above finished

grade in the area of the venting, including but not limited

to decks and porches, the following requirements shall

be satisfied.
1. INSTALLATION OF CARBON MONOXIDE

DETECTORS. At the time of installation of the side-wall,

horizontally vented, gas-fueled equipment, the installing

plumber or gas fitter shall observe that a hard-wired

carbon monoxide detector with an alarm and battery

backup is installed on the floor level where the gas

equipment is to be installed. In addition, the installing

plumber or gas fitter shall observe that a battery-

operated or hard-wired carbon monoxide detector

with an alarm is installed on each additional level of

the dwelling, building, or structure served by the side-

wall, horizontally vented, gas-fueled equipment. It shall

be the responsibility of the property owner to secure

the services of qualified licensed professionals for the

installation of hard-wired carbon monoxide detectors.
a. In the event that the side-wall, horizontally vented,

gas-fueled equipment is installed in a crawl space or

an attic, the hard-wired carbon monoxide detector with

alarm and battery backup may be installed on the next

adjacent floor level.
b. In the event that the requirements of this subdivision

cannot be met at the time of completion of installation,

the owner shall have a period of thirty (30) days to

comply with the above requirements, provided, however,

that during said thirty (30) day period, a battery-

operated carbon monoxide detector with an alarm shall

be installed.
2. APPROVED CARBON MONOXIDE DETECTORS.

Each carbon monoxide detector as required in

accordance with the above provisions shall comply with

NFPA 720 and be ANSI/UL 2034-listed and IAS-certified.

3. SIGNAGE. A metal or plastic identification plate

shall be permanently mounted to the exterior of the

building at a minimum height of eight (8) feet above

grade directly in line with the exhaust vent terminal for

the horizontally vented, gas-fueled heating appliance

or equipment. The sign shall read, in print size no less

than one-half (1/2) inch in size, “GAS VENT DIRECTLY

BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”
4. INSPECTION. The state or local gas inspector of the

side-wall, horizontally vented, gas-fueled equipment

shall not approve the installation unless, upon

inspection, the inspector observes carbon monoxide

detectors and signage installed in accordance with the

provisions of 248 CMR 5.08 (2)(a)(1 through 4).
(b) EXEMPTIONS: The following equipment is exempt

from 248 CMR 5.08 (2)(a)(1 through 4):
1. The equipment listed in Chapter 10 entitled

“Equipment Not Required To Be Vented” in the most

current edition of NFPA 54 as adopted by the Board,

and
2. Product-approved side-wall, horizontally vented,

gas-fueled equipment installed in a room or structure

separate from the dwelling, building, or structure used in

whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS – GAS

EQUIPMENT VENTING SYSTEM PROVIDED. When

the manufacturer of product-approved side-wall,

horizontally vented, gas-fueled equipment provides a

venting system design or venting system components

with the equipment, the instructions provided by the

manufacturer for installation of the equipment and the

venting system shall include:
1. Detailed instructions for the installation of the venting

system design or the venting system components; and
2. A complete parts list for the venting system design or

venting system.
(d) MANUFACTURER REQUIREMENTS – GAS

EQUIPMENT VENTING SYSTEM NOT PROVIDED.

When the manufacturer of product-approved side-

wall, horizontally vented, gas-fueled equipment does

not provide the parts for venting the flue gases, but

identifies “special venting systems,” the following

requirements shall be satisfied by the manufacturer:
1. The referenced “special venting systems” instructions

shall be included with the appliance or equipment

installation instructions, and
2. The “special venting systems” shall be product-

approved by the Board, and the instructions for that

system shall include a parts list and detailed installation

instructions.
(e) A copy of all installation instructions for all

product-approved side-wall, horizontally vented,

gas-fueled equipment, all venting instructions, all

parts lists for venting instructions, and/or all venting

design instructions shall remain with the appliance or

equipment at the completion of the installation.

Advertising
This manual is related to the following products: