Adjust the amount of time delayed before the relay is released after
the De-Actuation set point is reached. A maximum of 60 minutes is
possible, adjustable in 5-minute increments.
Default is 0000.
The Up key scrolls back up the Relay 1 Settings sub-menu branch.
The Down key leaves the Relay 1 Settings sub-menu branch and
returns to the Relay 1 Settings main menu item.
4.6
Buzzer Mode
B
B
U
U
Z
Z
Z
Z
E
E
R
R
D
D
i
i
s
s
a
a
b
b
l
l
e
e
The internal buzzer can be activated together with Relay 1 (and/or
Relay 2 – see Relay 2 sub-menu branch below) if ‘Enable’ is selected.
Pressing any of the keys during normal operation silences the buzzer.
Selecting ‘Disable’ in this sub-menu only disables the buzzer
activation for Relay 1. Buzzer operation respective to Relay 2 is set in
the ‘Relay 2 Settings’ sub-menu.
Note: If the buzzer is enabled for any of, or both the relays,
the first key press will silence the buzzer (buzzer
acknowledge) and a second key press is needed if any,
or both of the relays is set for ‘Latching’ mode. Refer to
3.1 above.
To configure the buzzer for Relay 2 operation, go the ‘Relay 2
Settings’ sub-menu.
Default is Disabled.
5.
Relay 2 Sub-menu Branch
Note: Per CSA Standard C22.2 No 152, Combustible Gas Detection
Instruments, relay alarm settings are limited to a
maximum of 60% LEL.
R
R
E
E
L
L
A
A
Y
Y
2
2
S
S
e
e
t
t
t
t
i
i
n
n
g
g
s
s
Press Enter to access the settings. The sub-menu structure is the same as
for Relay 1 Settings. Defaults are as follows:
5.1
Relay Mode