Cts-m17 configuration – RLE GD100 User Manual

Page 2

Advertising
background image

CTS-M17 Installation, Operation and Maintenance Manual

B84450-001-000 RG

May 12, 2005

1

CTS-M17 Configuration

Note: Defaults are used unless otherwise indicated under “User”.

No.

Setting

Default

User

1

Sensor Type/Gas Sensed

NAP-55A/Methane

2

Signal 20 mA

100 %LEL

3

Signal 4 mA

0 %LEL

4

Password

0017

5*

Relay 1

Enabled

6

Relay 1 Set point (Actuation)

20 %LEL

7

Relay 1 Release Point (De-Actuation)

15 %LEL

8

Relay 1 Actuation Delay

0 Minutes

9

Relay 1 De-Actuation Delay

0 Minutes

10*

Relay 2

Enabled

11

Relay 2 Set point (Actuation)

40 %LEL

12

Relay 2 Release Point (De-Actuation)

35 %LEL

13

Relay 2 Actuation Delay

0 Minutes

14

Relay 2 De-Actuation Delay

0 Minutes

15

Communication Protocol

Optomux

16

Digital Address

0001

17

Baud rate

4800

*Note: Relay set points are included in the software; however, relays are optional.