Cts-m17 configuration – RLE GD100 User Manual
Page 2

CTS-M17 Installation, Operation and Maintenance Manual
B84450-001-000 RG
May 12, 2005
1
CTS-M17 Configuration
Note: Defaults are used unless otherwise indicated under “User”.
No.
Setting
Default
User
1
Sensor Type/Gas Sensed
NAP-55A/Methane
2
Signal 20 mA
100 %LEL
3
Signal 4 mA
0 %LEL
4
Password
0017
5*
Relay 1
Enabled
6
Relay 1 Set point (Actuation)
20 %LEL
7
Relay 1 Release Point (De-Actuation)
15 %LEL
8
Relay 1 Actuation Delay
0 Minutes
9
Relay 1 De-Actuation Delay
0 Minutes
10*
Relay 2
Enabled
11
Relay 2 Set point (Actuation)
40 %LEL
12
Relay 2 Release Point (De-Actuation)
35 %LEL
13
Relay 2 Actuation Delay
0 Minutes
14
Relay 2 De-Actuation Delay
0 Minutes
15
Communication Protocol
Optomux
16
Digital Address
0001
17
Baud rate
4800
*Note: Relay set points are included in the software; however, relays are optional.