CTS-M17 Installation, Operation and Maintenance Manual

B84450-001-000 RG

May 12, 2005

12

Enabled

5.2

Actuation Set point

Minimum = 5 %LEL. Maximum = 60 %LEL in 5 %LEL increments.

Default = 40 %LEL

5.3. De-Actuation Set Point

Minimum = 5 %LEL. Maximum = 60 %LEL in 5 %LEL increments.

Default = 35 %LEL.

6.

Range Adjustment – 4mA

C

C

O

O

N

N

C

C

4

4

m

m

A

A

0

0

0

0

0

0

%

%

L

L

E

E

L

L

This feature allows adjustment of the 4 mA point to non-zero gas

concentrations. The display will always read as low as 0000 %LEL, but the

concentration corresponding to 4 mA changes.

Maximum: 500 %LEL (see note 3 below)

Minimum: 0 %LEL

Note 1: An inverted response at the signal output can be achieved by

setting CONC4MA higher than CONC20MA.

Note 2: Changing the range in this fashion does not enhance the gas

measurement accuracy. e.g.: If there is an error of 1 %LEL,

it will still be an error of 1 %LEL even if the range is

reduced.

Note 3: Even though the 4mA point can be adjusted beyond

100%LEL, the product can only measure accurately to just

over 100%LEL, due to the response of the sensor. The range

up to 500%LEL is only provided for flexibility in the

installation.

IMPORTANT: Do not set CONC4MA and CONC20MA points

closer than 10 %LEL. If the unit finds these

points closer than 10%LEL on menu system exit,

the higher point will be automatically adjusted

until a minimum difference of 10%LEL is present.