Installation – Desa VSF30NT User Manual

Page 11

Advertising
background image

www.desatech.com

11

116307-01B

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping

and connections, internal and

external to unit, for leaks after

installing or servicing. Correct

all leaks at once.

WARNING: Never use an

open flame to check for a leak.

Apply a noncorrosive leak detec-

tion fluid to all joints. Bubbles

forming show a leak. Correct all

leaks at once.

CAUTION: For propane/LP

gas, make sure external regula-

tor has been installed between

propane/LP supply and heater.

See guidelines under

Connect-

ing to Gas Supply, page 9.

PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect appliance with its appliance main

gas valve (control valve) and equipment

shutoff valve from gas supply piping system.

Pressures in excess of 1/2 psig will damage

heater regulator.

INSTALLATION

Continued

2. Cap off open end of gas pipe where equipment

shutoff valve was connected.

3. Pressurize supply piping system by either

opening propane/LP supply tank valve for

propane/LP gas or opening main gas valve

located on or near gas meter for natural gas

or using compressed air.

4. Check all joints of gas supply piping system.

Apply a noncorrosive leak detection fluid to

all joints. Bubbles forming show a leak.

5. Correct all leaks at once.
6. Reconnect heater and equipment shutoff valve

to gas supply. Check reconnected fittings for

leaks.

Test Pressures Equal To or Less Than 1/2
PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Figure 12).
2. Pressurize supply piping system by either

opening propane/LP supply tank valve for

propane/LP gas or opening main gas valve

located on or near gas meter for natural gas

or using compressed air.

3. Check all joints from gas meter for natural gas

or propane/LP supply tank for propane/LP gas,

to equipment shutoff valve (see Figure 13 or 14,

page 12). Apply a noncorrosive leak detection

fluid to all joints. Bubbles forming show a leak.

4. Correct all leaks at once.
PRESSURE TESTING HEATER GAS
CONNECTIONS
1. Open equipment shutoff valve (see Figure 12).
2. For natural gas open main gas valve located

on or near gas meter. For propane/LP gas open

propane/LP supply tank valve.

3. Make sure control knob of heater is in the OFF

position.

4. Check all joints from equipment shutoff valve to

thermostat gas valve (see Figure 13 or 14, page

12). Apply a noncorrosive leak detection fluid

to all joints. Bubbles forming show a leak.

5. Correct all leaks at once.
6. Light heater (see Operating Heater, this page).

Check all other internal joints for leaks.

7. Turn off heater (see To Turn Off Gas to Appli-

ance, page 13).

8. Install refractory and front panel.

Install sediment trap in supply line as shown in

Figure 11, page 10. Locate sediment trap where

it is within reach for cleaning. Locate sediment

trap where trapped matter is not likely to freeze.

A sediment trap traps moisture and contaminants.

This keeps them from going into heater controls. If

sediment trap is not installed or is installed wrong,

heater may not run properly.
Install male connector and flex gas line to equipment

shutoff valve through hole provided in rear surround

as shown in Figure 11, page 10.
IMPORTANT:

Hold the pressure regulator and

connector with wrench when connecting it to gas

piping and/or fittings. Do not over tighten pipe

connection to regulator. The regulator body could

be damaged.

Figure 12 - Equipment Shutoff Valve

Open

Closed

Equipment
Shutoff Valve