Air for combustion and ventilation – Desa VSF30NT User Manual

Page 6

Advertising
background image

www.desatech.com

116307-01B

6

1. Determine the volume of the space (length x

width x height).

Length x Width x Height =__________cu. ft.

(volume of space)

Example:

Space size 20 ft. (6.1 m) (length) x

16 ft. (4.88 m) (width) x 8 ft. (2.44 m) (ceiling

height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is

supplied with grills or openings, add the volume

of these rooms to the total volume of the space.

2. Multiply the space volume by 20 to determine

the maximum Btu/Hr the space can support.

__________ (volume of space) x 20 = (Maxi-

mum Btu/Hr the space can support)

Example:

2560 cu. ft. (72.4 m

3

) (volume of space) x 20

= 51,200 (maximum Btu/Hr the space can support)

3. Add the Btu/Hr of all fuel burning appliances in

the space.

Vent-free heater

_____________ Btu/Hr

Gas water heater*

_____________ Btu/Hr

Gas furnace

_____________ Btu/Hr

Vented gas heater

_____________ Btu/Hr

Gas fireplace logs

_____________ Btu/Hr

Other gas appliances* + ____________ Btu/Hr

Total

= ____________ Btu/Hr

* Do not include direct-vent gas appliances. Di-

rect-vent draws combustion air from the outdoors

and vents to the outdoors.

Example:

Gas water heater

_____________ Btu/Hr

Vent-free heater

+ ____________ Btu/Hr

Total

= ____________ Btu/Hr

4. Compare the maximum Btu/Hr the space can

support with the actual amount of Btu/Hr used.

_________ Btu/Hr (maximum the space can support)

_________ Btu/Hr (actual amount of Btu/Hr used)

Example:

51,200 Btu/Hr (maximum the space

can support)

60,000 Btu/Hr (actual amount of

Btu/Hr used)

The space in the above example is a confined space

because the actual Btu/Hr used is more than the maxi-

mum Btu/Hr the space can support. You must provide

additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoin-

ing room. If the extra space provides an unconfined

space, remove door to adjoining room or add

ventilation grills between rooms. See Ventilation

Air From Inside Building.

B. Vent room directly to the outdoors. See Ventila-

tion Air From Outdoors, page 7.

AIR FOR COMBUSTION

AND VENTILATION

Continued

C. Install a lower Btu/Hr heater, if lower Btu/Hr size

makes room unconfined.

If the actual Btu/Hr used is less than the maximum

Btu/Hr the space can support,

the space is an un-

confined space. You will need no additional fresh

air ventilation.

WARNING: If the area in

which the heater may be oper-

ated is smaller than that defined

as an unconfined space or if the

building is of unusually tight

construction, provide adequate

combustion and ventilation air

by one of the methods described

in the National Fuel Gas Code,

ANSI Z223.1/NFPA 54 Section 5.3

or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building
This fresh air would come from an adjoining un-

confined space. When ventilating to an adjoining

unconfined space, you must provide two perma-

nent openings: one within 12" (30.4 cm) of the

ceiling and one within 12" (30.4 cm) of the floor

on the wall connecting the two spaces (see options

1 and 2, Figure 2). You can also remove door into

adjoining room (see option 3, Figure 2). Follow the

National Fuel Gas Code, ANSI Z223.1/NFPA 54,

Section 5.3, Air for Combustion and Ventilation for

required size of ventilation grills or ducts.

40,000
20,000
60,000

Figure 2 - Ventilation Air from Inside

Building

Or

Remove

Door into

Adjoining

Room,

Option 3

Ventilation Grills

Into Adjoining Room,

Option 2

12"

12"

Ventilation

Grills

into Adjoining

Room,

Option 1

Advertising
This manual is related to the following products: