Refrigeration service – Scotsman CME865W User Manual

Page 26

Advertising
background image

VAPOR VAPOR

TEMP. PRES. TEMP. PRESS.

(DEG F) (PSIG) DEG F) (PSIG)

-20

17

70

146

-18

18

72

150

-16

20

74

155

-14

21

76

161

-12

23

78

166

-10

24

80

171

-8

26

82

177

-6

28

84

182

-4

29

86

188

-2

31

88

194

0

33

90

200

2

35

92

206

4

37

94

212

6

39

96

219

8

41

98

225

10

43

100

232

12

46

102

239

14

48

104

246

16

50

106

253

18

53

108

260

20

55

110

268

22

58

112

275

24

60

114

283

26

63

116

291

28

66

118

299

30

69

120

307

32

72

122

316

34

75

124

324

36

78

126

333

38

81

128

342

40

85

130

351

42

88

132

360

44

91

134

370

46

95

136

379

48

99

138

389

50

102

140

399

52

106

142

409

54

110

144

420

56

114

146

430

58

118

148

441

60

123

150

452

62

127

152

464

64

132

154

475

66

136

156

487

68

141

158

499

Pressure-Temperature Chart for R-404A

This ice machine uses R-404A refrigerant and polyolester oil. Do NOT
use mineral oil in this refrigeration system.

••

R-404A is a "Near Azeotrope" so liquid charging is required: See the
next page.

••

When the system is serviced, a special liquid line drier is required. It is
included with replacement compressors.

••

R-404A (HP62) is not compatible with mineral oil, so these ice
machines use Polyolester oil. Polyolester oil absorbs water very
easily. When one of these refrigeration systems is opened for service,
it must be re-sealed as soon as possible (15 minutes maximum).

••

Special leak detection equipment is required to locate small refrigerant
leaks. Usually a leak detector capable of detecting a Halongenated
refrigerant or HFC-134A will work. Check with the leak detector
manufacturer if in doubt.

Access Valves: To use the access valves:

••

Remove the cap from the stem, use a 3/16" allen wrench to check
that the valve is CLOSED. The remove the core cap.

••

Close the valve and replace the caps when the job is finished.
The valve must be closed and the caps must be on or the valve
will leak.

General Information:

Work on the refrigeration system should only be done when it is certain
that the system needs repair.

••

Refrain from checking refrigeration pressures without reason.
Visual inspection of the water system, observation of the ice
formation, amp draw, voltage, and other techniques will lead to proper
diagnosis.

••

If gauges must be used, don’t always check the high side pressure. If
the condenser is clean and seems to be operating correctly, it most
likely is.

••

If gauges must be used, use very short hoses to minimize refrigerant
discharged into the air.

••

Refrigerant should not be added except as a way to determine the
proper operation of the product. If the system was low on refrigerant,
there is a leak, and it must be found and repaired.

••

This system has a critical charge, it must be recharged with the
correct amount of refrigerant as listed on the nameplate of the ice
machine, or performance will suffer.

••

Anytime the refrigeration system has been opened, the dryer should
be replaced. Note: Only a HFC type dryer can be used.

••

When brazing the tubing connections to components such as the
TXV, the component must be protected by heat sink material.

Recover, reclaim or recycle refrigerant. The method chosen is up to
the service company. Any refrigerant placed into a Scotsman ice machine
must meet ARI spec 700-88. Reclaim programs are available through
most refrigerant wholesalers.

REFRIGERATION SERVICE

CME865W & CME1002W

December, 1994

Page 26