Installation – Desa CGCFTP User Manual

Page 18

Advertising
background image

www.desatech.com

111044-01F

18

4. Apply pipe joint sealant lightly to male threads

of gas connector attached to flexible gas line/

equipment shutoff valve (see Figure 26).

5. Check all gas connections for leaks. See

Checking Gas Connections.

6. Replace branch support back into fireplace.

Feed flexible gas line into fireplace base area

while replacing branch support. Make sure

the entire flexible gas line is in fireplace base

area. Reattach branch support to fireplace with

screws removed in step 2 on page 17.

INSTALLATION

Continued

Figure 26 - Attaching Flexible Gas Line

to Equipment Shutoff Valve

Flexible Gas Line from
Fireplace Gas Regulator
Provided with Fireplace

To Fireplace
Gas Regulator

Equipment Shutoff
Valve Provided by
Installer

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping

and connections, internal and

external to unit, for leaks after

installing or servicing. Correct

all leaks at once.

WARNING: Never use an

open flame to check for a leak.

Apply a noncorrosive leak detec-

tion fluid to all joints. Bubbles

forming show a leak. Correct all

leaks at once.

CAUTION: Make sure exter-

nal regulator has been installed

between propane/LP supply and

fireplace. See guidelines under

Connecting to Gas Supply,

page 16.

PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect appliance with its appliance main

gas valve (control valve) and equipment

shutoff valve from gas supply piping system.

Pressures in excess of 1/2 psig will damage

heater regulator.

2. Cap off open end of gas pipe where equipment

shutoff valve was connected.

3. Pressurize supply piping system by either

opening propane/LP supply tank valve for

propane/LP gas or opening main gas valve

located on or near gas meter for natural gas

or using compressed air.

4. Check all joints of gas supply piping system.

Apply a noncorrosive leak detection fluid to

gas joints. Bubbles forming show a leak.

5. Correct all leaks at once.
6. Reconnect heater and equipment shutoff valve

to gas supply. Check reconnected fittings for

leaks.

Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Fig-

ure 27).

2. Pressurize supply piping system by either

opening propane/LP supply tank valve for

propane/LP gas or opening main gas valve

located on or near gas meter for natural gas

or using compressed air.

3. Check all joints from gas meter for natural

or propane/LP supply to equipment shutoff

valve (see Figures 28 and 29, page 19). Ap-

ply a noncorrosive leak detection fluid to gas

joints. Bubbles forming show a leak.

4. Correct all leaks at once.

Figure 27 - Equipment Shutoff Valve

Open

Closed

Equipment
Shutoff
Valve

PROPANE/LP
To External
Regulator


NATURAL
To Gas Supply