e-TRIM Operations Manual
Appendix A – e-TRIM Modbus Registers
The following list is a description of the relevant Modbus registers in the e-TRIM system. For
communications, the e-TRIM supports Modbus on the Host 485 port and ModbusTCP through
Ethernet.
11
Active burner bitmap
14
Modbus address
15
Master Setpoint (2 decimal places)
16
Deviation alarm band setpoint (2 decimal places)
17
Out of band alarm delay time
18
Alarm disable bitmap
19
Alarm bitmap, burners 1 - 16.
20 - 35
O
2
readings, sensors 1 - 16, 2 decimal places.
68 - 83
High Fire ON, sensors 1 - 16.
116 - 131
O
2
trim delay, sensors 1 - 16.
132 - 147
O
2
trim interval time, sensors 1 - 16.
148 - 163
O
2
alarm state, sensors 1 - 16.
0 = normal, 1 = bad communications, 2 = out of and pending, 3 = out
of band.
164 - 179
Alarm delay timer (sec), sensors 1 = 16.
180 - 195
O
2
offset, sensors 1 - 16.
220 - 235
Slave communications status, boards 1 - 16. 0 = bad
communications, 4 = OK.
460
Critical alarm bitmap
461 - 476
Critical alarm, sensors 1 - 16.
477 - 492
Critical alarm set point, sensors 1 - 16.
493
Critical alarm acknowledge. 1 = acknowledged.
600
High fire total time (sec), sensor 1
601
High fire total time (hr), sensor 1
602
Low fire total time (sec), sensor 1
603
Low fire total time (hr), sensor 1
604
High fire timer, sensor 1
605
Low fire timer sensor 1
606 - 611
Timers for Sensor 2
612 - 617
Timers for sensor 3
618 - 623
Timers for sensor 4
624 - 629
Timers for sensor 5
630 - 635
Timers for sensor 6
636 - 641
Timers for sensor 7
642 - 647
Timers for sensor 8