5. Tips for Troubleshooting

can fuse T4A

If a malfunction occurs, a notification is given on the display
of the controller:

Operating control lamp

Warning symbol

Operating control lamp off

The power supply of the controller should
be checked if the control lamp goes out.

o.k.

no

The can fuse of the controller is defective.
It can be replaced after removal of the
front cover (spare fuse is enclosed in the
accessory bag).

Operating control lamp flashes red. On the display appears
the symbol

and the symbol

.

Sensor defect. An error code is shown
on the relevant sensor indication channel
instead of a temperature.

- 88.8

888.8

Line break. Check
the line.

Short-circuit.
Check the line.

Pt1000-temperature sensors pinched
off can be checked with an ohmmeter.
In the following the resistance values
corresponding to different temperatures
are listed.

°F

Ω

°F

Ω

14

961

131

1213

23

980

140

1232

32

1000

149

1252

41

1019

158

1271

50

1039

167

1290

59

1058

176

1309

68

1078

185

1328

77

1097

194

1347

86

1117

203

1366

95

1136

212

1385

104

1155

221

1404

113

1175

230

1423

122

1194

239

1442

Resistance values of the

Pt1000-sensors