Operating heater, Installation – Desa VF-30N-PJD User Manual

Page 14

Advertising
background image

www.desatech.com

111826-04C

14

INSTALLATION

Continued

PRESSURE TESTING HEATER GAS
CONNECTIONS

1. Open equipment shutoff valve (see Figure 13).

2. Open main gas valve located on or near gas

meter for natural gas or open propane/LP

supply tank valve.

3. Make sure control knob of heater is in the OFF

position.

4. Check all joints from equipment shutoff valve

to control valve (see Figure 14 or 15). Apply

noncorrosive leak detection fluid to all joints.

Bubbles forming show a leak.

5. Correct all leaks at once.

6. Light heater (see Operating Heater). Check

all other internal joints for leaks.

7. Turn off heater (see To Turn Off Gas to Appli-

ance, page 17 or 18).

Figure 13 - Equipment Shutoff Valve

Open

Closed

Equipment
Shutoff Valve

Figure 15 - Checking Gas Joints for

Propane/LP Gas

Control Valve Location

Propane/LP
Supply Tank

Equipment Shutoff Valve

Figure 14 - Checking Gas Joints for

Natural Gas

Gas Meter

Equipment Shutoff Valve

Control Valve
Location

3. Pressurize supply piping system by either

opening propane/LP supply tank valve for

propane/LP gas or opening main gas valve

located on or near gas meter for natural gas

or using compressed air.

4. Check all joints of gas supply piping system.

Apply noncorrosive leak detection fluid to all

joints. Bubbles forming show a leak.

5. Correct all leaks at once.

6. Reconnect heater and equipment shutoff

valve to gas supply. Check reconnected fit-

tings for leaks.

Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)

1. Close equipment shutoff valve (see Figure 13).

2. Pressurize supply piping system by either

opening propane/LP supply tank valve for

propane/LP gas or opening main gas valve

located on or near gas meter for natural gas

or using compressed air.

3. Check all joints from gas meter to equipment

shutoff valve for natural gas or propane/LP sup-

ply to equipment shutoff valve for propane/LP

(see Figure 14 or 15). Apply noncorrosive leak

detection fluid to all joints. Bubbles forming

show a leak.

4. Correct all leaks at once.

OPERATING HEATER

FOR YOUR SAFETY

READ BEFORE LIGHTING

WARNING: If you do not fol-

low these instructions exactly,

a fire or explosion may result

causing property damage, per-

sonal injury or loss of life.

A. This appliance has a pilot which must be

lighted by hand. When lighting the pilot,

follow these instructions exactly.

B. BEFORE LIGHTING smell all around the

appliance area for gas. Be sure to smell next

to the floor because some gas is heavier than

air and will settle on the floor.

Advertising