Westermo RFI-xx User Manual

Page 17

Advertising
background image

17

6641-22305

Ethernet TX
electrical specification

ieee std 802.3. 2005 edition

Data rate

10 Mbit/s or 100 Mbit/s, manual or auto

Duplex

Full or half, manual or auto

Circuit type

TNV-1

Transmission range

Up to 150 m (492 ft) with CAT5e cable or better*

isolation to

All other

Connection

rJ-45 auto MDi/MDi-X

shielded cable

Not required, except when installed in railway applications as
signalling and telecommunications apparatus and located close
to rails*

Conductive housing

Yes

Number of ports

2

* NOTE! railway installation close to the rails.
To minimise the risk of interference, a shielded cable is recommended when the cable is located
inside 3 m boundary to the rails and connected to this port.
The cable shield should be properly connected (360°) to an earthing point within 1 m from this
port. This earthing point should have a low impedance connection to the conductive enclosure of
the apparatus cabinet, or similar, where the unit is built-in. This conductive enclosure should be
connected to the earthing system of an installation and may be directly connected to the protective
earth. refer also to "safety" section.

IO / Relay output
Connect resistance

30 W

isolation to

All other

Connection

Detachable screw terminal

Connector size

0.2 – 2.5 mm

2

(AWG 24 – 12)

Maximum voltage/current

60 VDC / 80 mA

IO / Digital input
Voltage levels

Logic one >12V, Logic zero <1V

isolation to

All other

Connection

Detachable screw terminal

Connector size

0.2 – 2.5 mm

2

(AWG 24 – 12)

Maximum voltage

60 VDC

USB
electrical specification

UsB 2.0 host interface

Data rate

Up to 12 Mbit/s (full-speed mode)

Circuit type

seLV

Maximum supply current

500 mA

isolation to

All other except Console

Connection

UsB receptacle connector type A

Conductive housing

Yes