Current consumption calculation, Led indicators f4g-t4g – Westermo RFI-xx User Manual

Page 26

Advertising
background image

26

6641-22305

Position

Direction*

Description

1

in/Out

Bi_DA+

2

in/Out

Bi_DA–

3

in/Out

Bi_DB+

4

in/Out

Bi_DC+

5

in/Out

Bi_DC–

6

in/Out

Bi_DB–

7

in/Out

Bi_DD+

8

in/Out

Bi_DD–

shield

in/Out

Connected to Pe

+DC1

+DC2

COM

COM

RSTP

FRNT

VPN

ON

DC1
DC2

1

2

1

1

10/100/1000

10/100/1000

10/100 Base-TX

POWER

CONSOLE

IO

2

3

4

5

6

7

8

2

3

4

1

5

6

7

8

2

3

4

Position

Direction*

Description

rx

in

receive port

Tx

Out

Transmit port

LED indicators F4G-T4G

LED

Status

Description

Copper ports 1 – 4
Fibre ports 5 – 8

OFF

No link.

GreeN

Link established.

GreeN FLAsH

Data traffic indication.

YeLLOW

Port alarm and no link. Or if FrNT or rsTP mode,
port is blocked.

* Direction relative this unit.

* Direction relative this unit

Current consumption calculation

Current consumption values described for each interface is the current consumption
for that interface only. To calculate the total current consumption values shall be added
together.
For example a unit with the following configuration will be calculated as follows:

Used modules

Consumption

Power and CPU

410 mA @ 20 VDC

8 copper ports

144 mA @ 20 VDC

F4G

360 mA @ 20 VDC

Adding the values will give a total consumption of 914 mA @ 20 VDC.
external power supply must be rated to meet the calculated current.
Westermo recommends external power supply to be rated for a startup current which
is at least twice the calculated in service consumption. in the example above an external
power supply must be rated for at least 1828 mA for startup current.