Westermo EDW-120 User Manual

Page 23

Advertising
background image

23

6616-2211

* To minimise the risk of interference, a shielded cable is recommended when the cable is located inside 3 m

boundary to the rails and connected to this port.

The cable shield should be properly connected (360°) to an earthing point within 1 m from this port. This earthing

point should have a low impedance connection to the conductive enclosure of the apparatus cabinet, or similar,

where the unit is built-in. This conductive enclosure should be connected to the earthing system of an installation

and may be directly connected to the protective earth.

Ethernet 1

Electrical specification

IEEE std 802.3. 2000 Edition

Data rate

10 Mbit/s or 100 Mbit/s, auto-negotiated or manually
set by DIP-switches

Protocol

UDP, TCP, ICMP, HTTP and ARP

Duplex

Full- or half duplex, auto-negotiated or manually set by DIP-switches

Circuit type

TNV-1

Transmission range

100 m

Isolation to

Power 2 kV

rms

RS-232 1.5 kV

rms

RS-422/485 1.5 kV

rms

Connection

RJ-45 shielded, auto MDI/MDI-X

Shielded cable

Not required, except when installed in Railway applications as
signalling and telecommunications apparatus and located close
to rails*

Conductive housing

Isolated to all other circuits

Advertising