Ser ial comm uni c a ti ons – Hakko MONITOUCH V7 series User Manual

Page 148

Advertising
background image

3

7. PLC2Way

3-51

Ser

ial Comm

uni
c

a

ti

ons

• $s762

Periodical reading that is set in the [Temp. CTRL/PLC2Way Table Setting] dialog can be
suspended.

- [0]:

Periodical reading is performed.

- [Other than “0”]: Periodical reading is suspended.

If periodical reading of the temperature control network/PLC2Way table is performed
while the PLC2 memory is being accessed using a macro command, the macro
execution will be delayed (Fig. a). To avoid this, periodical reading can be suspended
using memory address $s762 (Fig. b).

• $s763

Forced execution of macro commands [TEMP_READ] and [TEMP_WRITE] using the
temperature control network/PLC2Way table

- [0]:

When any station that has failed is included in the specified table,
the macro command is not executed.

- [Other than “0”]: The macro command is forcibly executed to the stations that are

working properly.

TEMP_CTL $u100 2
TEMP_CTL $u110 2
TEMP_CTL $u120 2

TEMP_CTL $u300 2

T

t

TEMP_CTL $u100 2
TEMP_CTL $u110 2
TEMP_CTL $u120 2

TEMP_CTL $u300 2

T+t

T

T

$s762=1
TEMP_CTL $u100 2
TEMP_CTL $u110 2
TEMP_CTL $u120 2

TEMP_CTL $u300 2
$s762=0

$s762=1
TEMP_CTL $u100 2
TEMP_CTL $u110 2
TEMP_CTL $u120 2

TEMP_CTL $u300 2
$s762=0

t

(Fig. a)

Execution of macro “a”

Execution of macro “a”

Temperature control
network/PLC2Way table
periodical reading

V7 communication cycle

Execution of macro “b”

Execution of macro “b”

Temperature control
network/PLC2Way table
periodical reading

Temperature control
network/PLC2Way
table periodical reading

Temperature control
network/PLC2Way
table periodical reading

V7 communication cycle

• TEMP_READ

• TEMP_WRITE

• TEMP_CTL

• MOV, BMOV, BSET,

BCLR, BINV
When the PLC2 memory is
used for the above command:

(Fig. b)