Hakko MONITOUCH V7 series User Manual

Page 298

Advertising
background image

5

15. SIEMENS PLC

5-91

Co
nne

c

tio

n

to P

L

Cs

S5, S5 V4 (S5-115U, S5-135U, S5-155U, S7-300, S7-400)

S5 PG port

Communication parameters are automatically set.

S7-200PPI

S7-300MPI (HMI ADP), S7-300MPI (PC ADP)

• Set [MPI SETTING] in the [Comm. Parameter] dialog of the V-SFT editor.

Set different numbers for [Source No.] and [Local No.], and make sure that [Source No]
≤ [Node Cnt].
[Node Cnt] is equivalent to [Local No.] of the PLC. (For example, if [Local No.] is “13,”
[Node Cnt] is “15.”)

Item

Setting on PLC

V7 Comm. Parameter Setting

Baud rate

9600 bps

9600 bps

Parity

−

Even (fixed)

Transmission code

Data length

−

8 (fixed)

Stop bit

−

1 (fixed)

Item

Setting on PLC

V7 Comm. Parameter Setting

Baud rate

9600 bps

9600 bps

Port

2

2

Parity

Even (fixed)

−

Item

Setting on PLC

V7 Comm. Parameter Setting

Baud rate

38400 bps

HMI ADP

38400 bps (fixed)

PC ADP

38400 bps

Parity

−

Odd (fixed)

Transmission code

Data length

−

8 (fixed)

Stop bit

−

1 (fixed)

Local No. (PLC port number)

2

2

Item

MPI SETTING

Node Cnt

15/31/63/126

Source No. (V7 port number)

0