Checklist before installation

Table 5 Checklist before installation

Item Requirements

Result

Installation
site

Ventilation

•

There is a minimum clearance of 10 cm (3.94 in) around
the inlet and outlet air vents for heat dissipation of the

firewall chassis.

•

A ventilation system is available at the installation site.

Temperature

Operating: 0°C to 40°C (32°F to 104°F)
Non operating: –40°C to +70°C (–40°F to +158°F)

Relative humidity

Operating: 10% to 95% (noncondensing)
Non operating: 5% to 95% (noncondensing)

Cleanness

•

Dust concentration ≤ 3 × 10

4

particles/m

3

•

No dust on desk within three days

ESD prevention

•

The equipment and rack are well grounded.

•

The equipment room is dust-proof.

•

The humidity and temperature are at a proper level.

•

Wear an ESD-preventive wrist strap and make sure the
wrist strap makes good skin contact and is well

grounded when installing FRUs.

•

Put cards away on an ESD-preventive workbench, with
the PCB upward, or put them in ESD-preventive bags for

future use.

•

Touch only the edges, instead of electronic components

when observing or moving a removed interface card.

EMI prevention

•

Take effective measures to protect the power system from

the power grid system.

•

Separate the protection ground of the firewall from the

grounding device or lightning protection grounding

device as far as possible.

•

Keep the firewall far away from radio stations, radar and

high-frequency devices working in high current.

•

Use electromagnetic shielding when necessary.