4 mounting the protective covers, 5 checking the voltages on the sunny central, 1 checking the dc voltages – SMA SC 500CP-10-JP Installation Manual User Manual
Page 74

15 Commissioning
SMA Solar Technology AG
74
SCCP-JP-IA-A4-en-12
Installation Manual
15.4 Mounting the Protective Covers
Figure 29: Position of the protective covers in the Sunny Central
Procedure:
1. Make sure that all cables are attached to the cable support rails with cable ties.
2. Tighten all protective covers (torque: 5 Nm).
15.5 Checking the Voltages on the Sunny Central
15.5.1 Checking the DC Voltages
Position
Designation
A
Protective cover
B
Protective cover for the order option "EMC filtering device"
'$1*(5
Danger to life due to electric arcs if the multimeter is not connected correctly
Contacting the measurement points incorrectly can cause an electric arc. Electric arcs result in death or serious injury.
• Select the appropriate measurement range on the multimeter.
• Wear personal protective equipment.
• Select the correct measurement points.