6 related parameters, Parameter table, 6related parameters – Yaskawa 1000 Series Drive Option - Analog Monitor User Manual

Page 22

Advertising
background image

22

YASKAWA ELECTRIC TOBP C730600 40E 1000-Series Option AO-A3 Installation Manual

6 Related Parameters

6

Related Parameters

The parameters outlined in the following sections are used to set up the unit for operation

with the option. Set parameters as needed. Parameter setting methods can be found in the

drive unit Instruction Manual.

Parameter Table

Table 5 Related Parameters

No.

(Addr.

Hex)

<1> The unit outputs voltage while this parameter is being adjusted. Voltage levels can be adjusted to match the

specifications of an external meter.

Name

Description

Values

F4-01

(391)

Terminal V1 Monitor Selection

Sets the monitor signal for output from
terminal V1. Set this parameter to the last
three digits of the desired U†-†† monitor.
Some U parameters are available only in
certain control modes.
For example, enter “103” for U1-03.

Default when installed
to drive: 102 (output
frequency)
Default when installed
to energy-saving unit:
000 (reserved)
Range: 000 to 999

F4-02

(392)

Terminal V1 Monitor Gain

Sets the gain for voltage output via terminal
V1, where 100% equals 10 V output.
Terminal output voltage is limited to 10 V.

Default: 100.0%
Min: -999.9
Max: 999.9

F4-03

(393)

Terminal V2 Monitor Selection

Sets the monitor signal for output from
terminal V2. Set this parameter to the last
three digits of the desired U†-†† monitor.
Some U parameters are available only in
certain control modes.
For example, enter “103” for U1-03.

Default when installed
to drive: 103 (output
voltage)
Default when installed
to energy-saving unit:
000 (reserved)
Range: 000 to 999

F4-04

(394)

Terminal V2 Monitor Gain

Sets the gain for voltage output via terminal
V2, where 100% equals 10 V output.
Terminal output voltage is limited to 10 V.

<1>

Default: 50.0%
Min: -999.9
Max: 999.9

F4-05

(395)

Terminal V1 Monitor Bias

Sets the amount of bias added to the voltage
output via terminal V1.

<1>

Default: 0.0%
Min: -999.9
Max: 999.9

F4-06

(396)

Terminal V2 Monitor Bias

Sets the amount of bias added to the voltage
output via terminal V2.

<1>

Default: 0.0%
Min: -999.9
Max: 999.9

F4-07

(397)

Terminal V1 Signal Level

Sets the voltage level for the analog output.
0: 0 to +10 Vdc
1: -10 to +10 Vdc

Default: 0
Range: 0, 1

F4-08

(398)

Terminal V2 Signal Level

Default: 0
Range: 0, 1

Advertising