YASKAWA ELECTRIC TOBP C730600 41F 1000-Series Option DO-A3 Installation Manual
Table 6 Binary Coded Output (F5-09 = 1)
Coded Output
Description
TB2
P1-PC
P2-PC
P3-PC
P4-PC
0
Normal operation (no fault)
0
0
0
0
1
oC, GF (Overcurrent)
1
0
0
0
2
ov (Overvoltage)
0
1
0
0
3
oL2 (Unit overload)
1
1
0
0
4
oH, oH1 (Unit overheat)
0
0
1
0
5
oS (Overspeed)
1
0
1
0
6
Not used
0
1
1
0
7
rr, rH (Braking resistor overheat)
1
1
1
0
8
EF1 to EF12 (External fault)
0
0
0
1
9
CPF
, oFA
, oFb
, oFC
(Unit hardware fault)
1
0
0
1
A
oL1 (Motor overload)
0
1
0
1
B
Not used
1
1
0
1
C
Uv1, Uv2, Uv3 (Undervoltage)
0
0
1
1
D
dEv (Speed deviation)
1
0
1
1
E
PGo (PG disconnect)
0
1
1
1
F
Not used
1
1
1
1