6 Related Parameters

26

YASKAWA ELECTRIC TOBP C730600 41F 1000-Series Option DO-A3 Installation Manual

F5-05
(39D)

Terminal P5-PC Output Selection

Sets the function for contact output terminals
M1-M2, M3-M4, and photocoupler output
terminals P1 through P6.

<1>

When installed to drive
Default: 6
Range: 0 to 1A7
When installed to
energy-saving unit
Default: F
Range: 0 to 160

F5-06

(39E)

Terminal P6-PC Output Selection

When installed to drive
Default: 37
Range: 0 to 1A7
When installed to
energy-saving unit
Default: F
Range: 0 to 160

F5-07

(39F)

Terminal M1-M2 Output
Selection

When installed to drive
Default: F
Range: 0 to 1A7
When installed to
energy-saving unit
Default: F
Range: 0 to 160

F5-08
(3A0)

Terminal M3-M4 Output
Selection

When installed to drive
Default: F
Range: 0 to 1A7
When installed to
energy-saving unit
Default: F
Range: 0 to 160

F5-09
(3A1)

DO-A3 Output Mode Selection

0: Output terminals are each assigned
separate output functions.
1: Binary code output
2: Multi-function output (set functions in
parameters F5-01 through F5-08)

When installed to drive
Default: 0
Range: 0 to 2
When installed to
energy-saving unit
Default: 2
Range: 2

<1> Refer to the unit Instruction Manual for more information on setting the F5 parameters.

No.

(Addr.

Hex)

Name

Description

Values