Yaskawa APOGEE FLN User Manual
Page 20

YASKAWA TOEP YAICOM 10A Z1000 Bypass Network Protocol Apogee FLN Technical Manual
20
Table 4 .1 - APOGEE FLN Application 2721 Point Number Summary
Point
Number
Point
Type
Point Name
Factory Default
(SI Units)
Engr. Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On
Text
Off
Text
Z1000
Parameter
84
LAO
PID FB RMDS
0
–
1
0
–
–
b5-12
85
LAO
PID FB RMDL
0
PCT
1
0
–
–
b5-13
86
LAO
PID FB RMDT
1
SEC
0.1
0
–
–
b5-14
{87}
LAI
PID OUT CAP
0
PCT
0.01
0
–
–
U5-14
{88} LAI
PID
REF
0
PCT
0.01
0
–
–
U5-04
{89}
LAI
COMM ERR CD
0
–
1
0
–
–
U1-19
90 LDO
COMM
FLT
ENA ENABLE
–
1
0 ENABLE
DISABLE
Z3-11
91
LAO
CBL LOSS FRQ
0
HZ
0.01
0
–
–
Z3-10
92 LAO
CBL
LOSS
TMR
2
SEC
0.1
0
–
–
Z3-06
{93}
LDI
OK.FAULT
OK
–
1
0
FAULT
OK
UB-06 (Bit 2)
{94} LDO RESET
FAULT
NO
–
1
0
RESET NO
–
{95}
LDI
DRV COMM ERR
NO FLT
–
1
0
FAULT
NO FLT
–
{96} LDO EXTERNAL
FLT
OK
–
1
0
FAULT OK
–
{97}
LDI
MF IN 5 MON
OFF
–
1
0
ON
OFF
UB-02 (Bit 6)
Bypass DI-7
{99} LAI ERROR
STATUS
0
–
1
0
–
–
–
<1> Note: For pt 35 to work properly, set Z2-02=22 Run Enable (Safety)