YASKAWA TOEP YAICOM 10A Z1000 Bypass Network Protocol Apogee FLN Technical Manual

23

Continue at Preset Speed with Alarm

In this mode, CBL LOSS TMR (POINT 92) is set to the desired interval, CBL LOSS FRQ (POINT 91) is set to the desired preset speed and
Z3-05 is set to “4”. If the time between messages exceeds the timeout interval, the drive’s speed command, INPUT REF 1, (Point 60) is set
to the CBL LOSS FRQ (POINT 91) and the drive continues running at this new speed. COMM FLT ENA (POINT 90) must be set to ‘On’.

Stop with Fault (FB14)

COMM FLT ENA (POINT 90) must be set to ‘On’. In this mode, CBL LOSS TMR (POINT 92) is set to the desired interval and parameter
F6-03 is set to a value of 0,1 or 2. If the time between messages exceeds the timeout interval, the drive’s speed command, INPUT REF 1,
(Point 60) is set to 0. The stopping method is determined by the setting of F6-03. An FB14 drive fault will be set and an EF0 will be sent to
the drive. The drive behavior is determined by the setting of parameter F6-03.

F6-03 = 0 selects Ramp to Stop. The deceleration time or the slope of the ramp is determined by the setting of drive

parameter C1-02.

F6-03 = 1 selects Coast to Stop. The drive does not attempt to control the rate of deceleration.

F6-03 = 2 selects Fast Stop. The deceleration time is determined by the setting of drive parameter C1-09.