Yaskawa BACnet Option User Manual

Bacnet, Option installation guide, Warning

Advertising
background image

BACnet

®

Option

Installation Guide

Yaskawa America, Inc. –

www.yaskawa.com

IG.AFD.23.BACnet, Page 1 of 12

Date: 7/07/2011 Rev: 11-07

Applicable products: E7U, E7B

1

, E7L

1

,

P7U, P7B

1

and P7L

1

drives

1. Unpack the BACnet Option and verify that all components are present

and undamaged.

Note: 1:Cables UWR00567-2 and UWR00567-3 are used for Bypass
products and must be ordered separately.

2. Prepare the drive.

Connect the drive as shown in the appropriate technical manual or
supplied schematic as with the Bypass products. Apply power to the
drive or Bypass panel and verify that the drive functions correctly. This
includes running the drive through the operator keypad (or the Bypass
keypad, in case of Bypass products). Refer to the appropriate technical
manual or schematics for information on connections and operation.

Remove power and wait for the drive charge lamp to be completely
extinguished. Measure and verify that the drive’s DC BUS voltage is at
a safe level.

Remove the operator keypad and all drive covers.

For Bypass products, make sure that the disconnect is in the OFF
position, then loosen the cover screws and open the cover.

Part

Qty.

BACnet Option (UTC000220)

1

Installation Guide (IG.E7.23)

1

UWR00567-1 (Drive Connection Cable - Included)

12” Cable

1

UWR00567-2 (Drive Connection Cable – Optional)

20” Cable

Opt

UWR00567-3 (Drive Connection Cable – Optional)

78” Cable

Opt

WARNING

Dangerous voltages in excess of 400VDC (230V drives) or 800VDC
(460V drives) are present at the DC bus terminals of the drive.

Advertising