Bacnet, Option installation guide – Yaskawa BACnet Option User Manual

Page 6

Advertising
background image

Yaskawa America, Inc. –

www.yaskawa.com

IG.AFD.23.BACnet, Page 6 of 12

Date: 7/07/2011 Rev: 11-07

BACnet

®

Option

Installation Guide

12. Analog Inputs (AI)

Note: 1: A13 through A19 are for diagnostics purposes only.

13. Analog Outputs (AO)

14. Binary Inputs (BI)

15. Binary Outputs (BO)

Note: 1: BO5, BO6 and BO7 are for broadcast messages only. Only RUN/STOP and frequency reference messages may be sent.

Obj ID

Name

Scale

Units

AI1

Analog Input 1 Level

0.1

%

AI2

Analog Input 2 level

0.1

%

AI3

1

Modbus Timeout Cnt

Not Scaled

No Units

AI4

1

Modbus Checksum Cnt

AI5

1

Modbus Error

AI6

1

Display Format o1-03

AI7

1

Scale Format b5-20

AI8

1

Inverter Model o2-04

AI9

1

Rated Current n9-01

Obj ID

Name

Scale

Units

AO1

Analog Output 1 Level

0.1

%

AO2

Analog Output 2 Level

0.1

%

Obj ID

Name

ON Text

OFF Text

BI1

Multi Function Input 1

ON

OFF

BI2

Multi Function Input 2

ON

OFF

BI3

Multi Function Input 3

ON

OFF

BI4

Multi Function Input 4

ON

OFF

BI5

Multi Function Input 5

ON

OFF

BI6

Multi Function Input 6

ON

OFF

BI7

Multi Function Input 7

ON

OFF

BI8

Multi Function Output 1

ON

OFF

BI9

Multi Function Output 2

ON

OFF

Obj ID

Name

ON Text

OFF Text

BO1

Multi Function Output 1

ON

OFF

BO2

Multi Function Output 2

ON

OFF

BO3

Multi Function Output 3

ON

OFF

BO4

Ref Sel: PI Set point

ON

OFF

BO5

1

Ref Sel: Terminal S5 IN

ON

OFF

BO6

1

Ref Sel: Terminal S6 IN

ON

OFF

BO7

1

Ref Sel: Terminal S7 IN

ON

OFF