16. Analog Values (AV)

Obj ID

Obj Name

Bit

Name

Read/ Write

Scale

Unit

AV1

Operation Cmd

0

Run Forward

Write

Bit Field

1

Run Reverse

2

External Fault (EF0)

3

Fault Reset

4

ComNet

5

ComRef

6

Multi-Function Input 3

7

Multi-Function Input 4

8

Multi-Function Input 5

9

Multi-Function Input 6

10

Multi-Function Input 7

11

Multi-Function Input 8

12

Reserved

13

Reserved

14

Reserved

15

Reserved

AV2

Frequency Cmd

Scaled by o1-03 with Units selected by Parameter o1-09

Write

o1-03

o1-09

AV3

1

PI Setpoint Cmd

Reference Select PID (BO4) must be set to ON in order to use AV3
Scaled by Parameter b5-20 with Units by b5-31

Write

b5-20

b5-31

AV4

MF Outputs Cmd

0

Relay Output

Write

1

PCH1

2

PCH2

3

Reserved

4

Reserved

5

Reserved

6

Error Relay Enable (Must be Set Before bit 7)

7

Error Relay

8-15

Reserved

AV5

Reference Select

Cmd

0

Reserved

Write

Bit Field

1

Ref. Select PID

2-11

Reserved

12

Ref. Select Terminal 5

13

Ref. Select Terminal 6

AV6

Drive Status

0

@ Run

Read

Bit Field

1

@ Reverse

2

@ Inverter Ready

3

@ Fault

4

@ Data Set Error

5

@ Relay Output

6

@ PCH1

7

@ PCH2

8-15

Reserved

Note

1

In order to use AV3
(Ref Sel: PI Setpoint)

Set b5-01 = 1
Set BO4 (Ref Sel: PI Setpoint) to ON
Set the desired value in AV3 in percent of max frequency