Deleted Parameters:

The following parameters are no longer present, and their function descriptions in Section 5 of the
Technical Manual are not applicable:

b1-05

Zero-Speed Operation

b7-01 & b7-02

Droop Control Setup

b9-01 & b9-02

Zero Servo Setup

C3-05

Slip Compensation V/f

C5-01 thru C5-07

Automatic Speed Regulator

C8-08

AFR Gain

C8-30

Carrier in tune

d5-01 thru d5-06

Torque Control Parameters

E2-04, E2-06 thru E2-09

Open Loop Vector Parameters

F1-01 thru F1-14

Pulse Generator / Encoder Setup Parameters

L7-01 thru L7-04

Torque Limits

o1-03

Display Scaling

o1-04

Display Units

Startup Procedure:

1.

Set the Parameter Access Level to "Advanced" (Section 2.2C)

(2)

.

2.

Set the V/f pattern. This pattern can be a standard (preset) V/f pattern or a custom V/f
pattern. Preset V/f patterns can be found in Table 5-4 (Section 5.48)

(2)

. A preset V/f pat-

tern is selected by the setting of E1-03. When one of these preset V/f patterns is
employed, parameter E1-01 (Input Voltage Setting) needs to be set at the motor’s name-
plate value. If a custom V/f pattern is desired, set E1-03 = F (User Defined V/f) and use
Figure 1 and parameters E1-04 thru E1-13 to set it up (Section 5.48)

(2)

.

Figure 1. V/f Characteristics Set by E1-04 thru E1-13

This Page: | Change | 0 | 4/18/97 |

Page 3 of 4

Doc. No. 02Y00025-0420

Vmax

( E1-05 )

V

B

( E1-12 )

Vbase

( E1-13 )

OUTPUT

VOLTAGE

V

A

( E1-08 )

Vmin

( E1-10 )

Fmin

F

A

Fbase

F

B

Fmax

( E1-09 )

( E1-07 ) ( E1-06 )

( E1-11 )

( E1-04 )

OUTPUT FREQUENCY