Electronic lineshaft with registration, 0 new alarm and fault codes, 0 changed defaults of parameters – Yaskawa G5 Electronic Line Shaft User Manual
Page 14
 
Electronic Lineshaft with Registration
Date: 07/01/04, Rev: 04-07
Sheet 14 of 14
TM.G5SW.047
6.0 New Alarm and Fault Codes
Alarm Display
Name
Description
Corrective Action
FOL_ALM
Following Alarm
Following Alarm
The position error between 
the master and follower 
exceeded the allowable 
amount. (See P1-07,  P1-08) 
Check for physical 
obstruction of the follower 
motion. 
Fault Display
Name
Description
Corrective Action
FOL_FLT
Following Fault
Following Error
The position error between 
the master and follower 
exceeded the allowable 
amount. (See P1-07, P1-08) 
Check for physical 
obstruction of the follower 
motion. 
Encr. Fault
CCW only in ELS
Encoder Direction
Fault
When in Lineshaft mode, 
parameter F1-05 must be set 
to 0 (CCW direction). 
Set F1-05 to 0 (CCW) and 
swap wires on the PG-W2 
card, terminals 3 and 4. 
OPE12
Carrier 2.5, 5, 10
Carrier Frequency
Setting Fault
This software requires the 
carrier frequency to be set at 
2.5, 5.0, or 10 kHz. 
Set C6-01 to 2.5, 5.0, or 10 
kHz. 
 
 
 
 
7.0 Changed Defaults of Parameters
Parameter Original
VSG114814
Function
A1-01
Quick Advanced Access
Level
A1-02
Open Loop Vector
Flux Vector
Control Mode
C6-01
15.0 kHz
10.0 kHz
Max Carrier Frequency