Install the EDS File and Configure the Drive on the DeviceNet Network

To simplify the drive configuration, EDS file can be obtained at

www.yaskawa.com

. Select Downloads, By Inverter Drives, By Product, and Network Comms-DeviceNet.

Then select the appropriate EDS file based on the drive series and the latest version from those listed. EDS files for individual drive models are compressed into a single
Zip file.
Install the EDS file into the DeviceNet configuration tool (i.e. RSNetworx

®

for DeviceNet). There is a separate EDS file for each drive model. Verify that the correct EDS

file has been installed for the drive model configured. Refer to the documentation that came with the master configuration tool for information on installing EDS files and
configuring a DeviceNet node.

‰

LED Status Indicators and Diagnostics

LED Display

PWR

MS

NS

WD

Content

Cause

Solution

„

The drive is not powered

„

Check the drive main circuit wiring

„

Turn

power

on.

Off Off Off Off

Power

Off

„

The option board is not connected

correctly or securely to the drive.

„

Turn Off drive power.

„

Check the connection of the option board
to the 2CN connector on the drive,

„

Turn

power

on.

Solid
Green

Off

Off

Solid Red CPU Fault

„

The option board CPU is being

initialized or has a fault.

„

Cycle power to the drive.

„

If the fault persists, replace the option
board.

Solid
Green

Flashing
Green

Off

Flashing
Green

Option Board Initialization

„

Option board Initialization.

„

Wait for initialization to complete

„

If initialization does not complete within
several seconds, cycle power to the drive.

„

If initialization does not complete after
power cycling the drive, replace the option
card

Solid
Green

Flashing
Red

Off

Flashing
Green

Recoverable Option Board
Fault

„

An incorrect DIP switch setting or

other recoverable fault.

„

Check baud rate setting (DIP switch, DR1
and DR0), and then cycle power to the
drive.

„

If the fault persists, replace the option
board.

Solid
Green

Solid
Red

Off

Flashing
Green

Unrecoverable Option Board
Fault

„

An un-recoverable fault

„

Cycle power to the drive.

„

If the fault persists, replace the option
board.

Solid
Green

Solid
Red

Solid
Red

Flashing
Green

Baud Rate Setting Fault

„

DR1 and DR0 are both set to ON.

„

Set the baud rate switches correctly.

„

Cycle power to the drive.

Solid
Green

Solid
Green

Flashing
Red

Flashing
Green

Communication Timeout

„

A master communication timeout.

„

Check network termination.

„

Check

network

wiring.

„

Check that the communication bus wiring
is separated from the main circuit wiring.

Solid
Green

Solid
Green

Solid
Red

Flashing
Green

Communication Error

„

Unrecoverable communication fault.

„

Check if other device’s MAC ID is not
unique per the network.

„

Check if the master is correctly configured.

„

Check if the end termination resistor is
correctly connected to the communication
bus.

„

Check if the communication device is
correctly connected per wiring diagrams.

„

Check if the communication bus wiring is
separated from the main circuit wiring.

Solid
Green

Solid
Green

Flashing
Green

Flashing
Green

Normal Not Communicating

„

Connected to a DeviceNet network

but not communicating

„

Send explicit message or I/O message
from the master as necessary.

Solid
Green

Solid
Green

Solid
Green

Flashing
Green

Normal Communicating

„

Connected to a DeviceNet network

and communicating normally

-


Note: 1: Do not install, remove or handle a network card connected to the drive with power applied to the drive. Remove power from the drive and wait for the charge lamp to

be completely extinguished. Wait at least five additional minutes for the drive to be completely discharged. Measure the DC bus voltage and verify that it is at a safe
level.

2: When cycling power to the drive, make sure that the drive is fully discharged prior to reapplying power.