Analog Output Option Card

AO-08 or AO-12



Table 4. Selecting the Monitored Output (GPD515/G5)

Terminal Parameter

Set

Value

Control

Method

(1)

Output Monitor

Scaling

1

0, 1, 2, 3

Frequency Reference

10V/100%

2

0, 1, 2, 3

Output Frequency

10V/100%

3

0, 1, 2, 3

Output Current

10V/drive rated current

5

1, 2, 3

Motor Speed

10V/100%

6

0, 1, 2, 3

Output Voltage 10V/200VAC

(400VAC)

7

0, 1, 2, 3

DC Bus Voltage 10V/400VDC

(800VDC)

8

0, 1, 2, 3

Output Power (kW)

10V/100%

9

2, 3

Torque Reference

10V/100%

15

0, 1, 2, 3

Terminal 13 Input

10V/10V

16

0, 1, 2, 3

Terminal 14 Input

10V/10V (20mA)

17

0, 1, 2, 3

Terminal 16 Input

10V/10V

18

0, 1, 2, 3

Motor Secondary Current (Iq)

10V/motor rated current

19

2, 3

Motor Exciting Current (Id)

10V/motor rated current

20

0, 1, 2, 3

Output Frequency After Soft-Start (SFS)

10V/100%

21

1, 3

ASR Input

10V/100%

22

1, 3

ASR Output

10V/motor rated current

23

1, 3

Speed Deviation / Speed Regulator Input

10V/100%

24

0, 1, 2, 3

PID Feedback

10V/100%

26

2, 3

Output Voltage Reference (Vq)

10V/230V (460V)

TD1

or

TD2

F4-01

or

F4-03

27

2, 3

Output Voltage Reference (Vd)

10V/230V (460V)

(1) Output available only when using one of the listed control methods (A1-02 setting):
0: V/Hz Mode, 1: V/Hz with Encoder (PG), 2: Open Loop Vector, 3: Closed Loop Flux Vector