Yaskawa Electric America, Inc. – www.drives.com

IG.AFD.51, Page 4 of 4

Date: 07/01/04, Rev: 04-07

Analog Output Option Card

AO-08 or AO-12

Table 5. Selecting the Monitored Output (F7/G7)

Terminal

Parameter

Set

Value

Control

Method

(1)

Output Monitor

Scaling

1 0,1,2,3,4 Frequency Reference

10V: Maximum output frequency

(0 ~ ± 10V possible)

2 0,1,2,3,4

Output Frequency

10V: Maximum output frequency

(0 ~ ± 10V possible)

3 0,1,2,3,4

Output Current

10V: Drive rated output current

(0 ~ 10V, absolute value)

5 1,2,3,4

Motor

Speed

10V: Maximum output frequency

(0 ~ ± 10V possible)

6 0,1,2,3,4

Output

Voltage

10V: 200VAC (400VAC)

7

0,1,2,3,4

DC Bus Voltage

10V: 400VDC (800VDC)

8 0,1,2,3,4

Output

Power

10V: Drive capacity kW

(0 ~ ± 10V possible)

9 2,3,4

Torque

Reference

10V: Motor rated torque

(0 ~ ± 10V possible)

15 0,1,2,3,4

Terminal A1 Input

10V: 100% (at 10V input)

(0 ~ ± 10V possible)

16 0,1,2,3,4

Terminal A2 Input

10V: 100% (at 10V input)

(0 ~ ± 10V possible)

17 0,1,2,3,4

Terminal A3 Input

10V: 100% (at 10V input)

(0 ~ ± 10V possible)

18 0,1,2,3,4

Motor

Secondary Current (Iq)

10V: Motor rated secondary current

(0 ~ ± 10V possible)

19

2,3,4

Motor Excitation Current (Id)

10V: Motor rated secondary current

(0 ~ ± 10V possible)

20 0,1,2,3,4

Output Frequency after

Soft-Starter (SFS)

10V: Maximum output frequency

(0 ~ ± 10V possible)

21 1,3,4

ASR

Input

10V: Maximum output frequency

(0 ~ ± 10V possible)

22 1,3,4

ASR

Output

10V: Motor rated secondary current

(0 ~ ± 10V possible)

24 0,1,2,3,4

PID

Feedback

10V: Maximum output frequency

(0 ~ ± 10V possible)

26 2,3,4

Output Voltage Reference

(Vq)

10V: 200VAC (400VAC)

(0 ~ ± 10V possible)

27 2,3,4

Output Voltage Reference

(Vd)

10V: 200VAC (400VAC)

(0 ~ ± 10V possible)

32

2,3,4

ACR (q) Output

10V: 100%

(0 ~ ± 10V possible)

33

2,3,4

ACR (d) Output

10V: 100%

(0 ~ ± 10V possible)

36 0,1,2,3,4

PID Input (Error)

10V: 100%

(0 ~ ± 10V possible)

37 0,1,2,3,4

PID Output

10V: Maximum output frequency

(0 ~ ± 10V possible)

38 0,1,2,3,4

PID

Setpoint

10V: Maximum output frequency

42

(2)

4

Estimated Motor Flux

10V: Rated motor flux

43

(2)

4

Motor Flux Current

Compensation

10V: Motor rated secondary current

(0 ~ ± 10V possible)

44

3,4

ASR Output without Filter

10V: Motor rated secondary current

(0 ~ ± 10V possible)

TD1

or

TD2

F4-01

or

F4-03

45 3,4

Feed Forward Control

Output

10V: Motor rated secondary current

(0 ~ ± 10V possible)

(1) Output available only when using one of the listed control methods (A1-02 setting):

0: V/Hz, 1: V/Hz with Encoder (PG), 2: Open Loop Vector, 3: Closed Loop Flux vector, 4: Open Loop Vector 2

(2)

(2) G7 only.