Yaskawa DO-08 User Manual

Digital output option card do-08

Advertising
background image

Yaskawa Electric America, Inc. – www.drives.com

IG.AFD.56, Page 1 of 4

Date: 07/01/04, Rev: 04-07

Digital Output Option Card

DO-08

Grounding Terminal

4CN
Option Card A

2CN
Option Card C

3CN
Option Card D

Option Clip

Figure 1. DO-08 Option Card installation

Part Number:

DO-08.


Applicability.

F7, G7, GPD515/G5, G5HHP.

Note: If used in a GPD503/G3, or VCD703/VG3, refer
to Instruction Sheet 02Y00025-0350.

Introduction.

The Digital Output option board is

mounted on the drive’s Control Board and allows the
user to employ isolated type digital signals to monitor
status outputs of the drive (alarm signal, zero-speed
detection, etc.)

Receiving.

All equipment is tested against defect at

the factory. Report any damages or shortages evident
when the equipment is received to the commercial
carrier who transported the equipment.

Warning

: Hazardous voltage can cause severe injury

or death. Lock all power sources feeding the drive in
the “OFF” position.

Caution:

This option card uses CMOS IC chips. Use

proper electrostatic discharge (ESD) protective
procedures when handling the card to prevent I.C.
damage or erratic drive operation.

Important:

1. If this option is being installed in a drive with

an encoder (PG) feedback option card, that
card will need to be temporarily removed to
allow access to connector 3CN on the drive’s
control board and TD1 – TD11 on the DO-08
option card.

2. Before installing this option, a technically qualified

individual, who is familiar with this type of
equipment and the hazards involved, should read
this entire installation guide.

Installation and Wiring:

1. Disconnect all electrical power to the drive.
2. Remove the drive’s front cover.
3. Check that the “CHARGE” indicator lamp inside the

drive is off.

4. Use a voltmeter to verify that the voltage at the

incoming power terminals (L1, L2, L3) has been
disconnected.

5. Circuit Board Installation: See Figure 1.

a) Position the option card above the control board’s 3CN connector and gently press the card into place.
b) Connect the green ground wire to the grounding terminal on the main control board.

6. Wiring: Refer to Figure 2 and Table 2. Make wire connections between the DO-08 card and the drive, as well as all

peripheral devices. Observe the following:
a) Keep DO-08 (i.e. control circuit) wiring separate from main circuit input/output wiring. A separate metallic

grounded conduit with only the option card’s wiring running through it is preferred.

b) To prevent erroneous operation caused by noise interference, use shielded cable for control signal wiring, and

limit the distance to 50m (165 feet) or less.

c) Refer to the drive technical manual for additional information on the use of shielded cable.

7. Adjustment: There are no adjustments to be made on the Digital Output option card; however, drive parameters will

have to be reprogrammed for the desired output signal content. Refer to Table 3.

8. Reinstall and secure the drive’s front cover.
9. Place this instruction sheet with the drive’s technical manual.

Table 1. Specifications

Output Type

Quantity

Photocoupler Output

6 (common emitter)

Relay Contact Output

2 (independent)

Advertising