Digital output option card do-08 – Yaskawa DO-08 User Manual
Page 3

Yaskawa Electric America, Inc. – www.drives.com
IG.AFD.56, Page 3 of 4
Date: 07/01/04, Rev: 04-07
Digital Output Option Card
DO-08
Table 3. DO-08 Output Mode Selection
GPD515/G5
Parameter
F6-01 Setting
F7, G7
Parameter
F5-09 Setting
Output Type
Terminal
Output Content
TD5-TD11
Overcurrent (SC, OC, GF)
TD6-TD11 Overvoltage
(OV)
TD7-TD11
Drive Overload (OL2)
TD8-TD11
DC Bus Fuse Blown (FU, PUF)
TD9-TD11 Not
Used
TD10-TD11 Overheat
(OH)
TD1-TD2 Zero-Speed
0 0
Fixed
Data
TD3-TD4 Speed
Agree
TD5-TD11 Bit
0
TD6-TD11 Bit
1
TD7-TD11 Bit
2
TD8-TD11
Coded
Output,
See
Table 4
Bit 3
TD9-TD11 Zero-Speed
TD10-TD11 Speed
Agree
TD1-TD2 Running
1 1
Coded
Output
TD3-TD4 Minor
Fault
TD5-TD11 F5-01
TD6-TD11 F5-02
TD7-TD11 F5-03
TD8-TD11 F5-04
TD9-TD11 F5-05
TD10-TD11 F5-06
TD1-TD2 F5-07
- 2
Individually
Selectable
See Table 5
TD3-TD4 F5-08
Table 4. Details of DO-08 Coded Output
Bits 3, 2, 1, 0
Output Content
Bits 3, 2, 1, 0
Output Content
0000
No Fault
1000
External Fault (EFXX)
0001
Overcurrent (SC, OC, GF)
1001
Drive Hardware Fault (CPFXX)
0010
Overvoltage (OV)
1010
Motor Overload (OL1)
0011
Drive Overload (OL2)
1011
Not Used
0100
Drive Overheat (OH2)
1100
Power Loss (UV) (Including momentary power loss)
0101
Not Used
1101
Not Used
0110
Fuse Blown (FU)
1110
Not Used
0111
Not Used
1111
Cooling Fan Fault (Fan)