Table 3. GPD 515/G5, F7, and G7 Encoder Feedback Parameter List
Control
Method (2)
Digital Operator
Func
tion Group
Digital Operator
Disp
lay
Parameter Number
Parameter Name
Se
tting Ra
nge
Fa
c
tory
Se
tting
Cha
nge
During
Op
eratio
n
(1)
Data Selectio
n
V/f w/ PG
F
eed
b
ack
Flux
Ve
c
tor
PG Pulse/Rev
F1-01
PG Constant
0 to
60000
1024 X
O
O
PG Fdbk Loss
Sel
F1-02
Operation at
Open PG
Circuit
0 to 3
1
X
O
O
PG Overspeed
Sel
F1-03
Operation
Selection at
Overspeed
0 to 3
1
X
O
O
PG Deviation
Sel
F1-04
Operation
Selection at
Deviation
0 to 3
3
X
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
O O
PG Rotation
Sel
F1-05 PG
Rotation
0,1
0
X
0: Fwd = CCW
1: Fwd = CW
O O
PG Ramp PI/I
Sel
F1-07
Integral
Control during
Accel/Decel
0,1 0 X
0: Disabled
1: Enable
O X
PG Overspeed
Level
F1-08
Overspeed
Detection
Level
0 to
120%
115% X
O
O
PG Overspeed
Time
F1-09
Overspeed
Detection
Delay Time
0 to 2.0s
1.0s
X
O
O
PG Deviation
Level
F1-10
Speed
Deviation
Detection
Level
0 to 50%
10%
X
O
O
PG Deviation
Time
F1-11
Speed
Deviation
Detection
Delay Time
0 to 10s
0.5s
X
O
O
PG# Gear
Teeth 1
F1-12
Number of
Gear Teeth 1
0 to 1000
0
X
O
X
PG# Gear
Teeth 2
F1-13
Number of
Gear Teeth 2
0 to 1000
0
X
O
X
PGO Detect
Time
F1-14
PGO Detection
Time
0 to 10s
2s
X
O
O
PG
Option
Setup
Speed
Detection
Filter Selection
F1-15
Speed
Detection Filter
Selection
0, 1
1
X
0: No Average
1: 2 Scan Moving
Average
O O