Encoder feedback option card pg-x2 – Yaskawa PG-X2 User Manual
Page 8

Yaskawa Electric America, Inc. – www.drives.com
IG.AFD.60, Page 8 of 8
Date: 07/01/04, Rev:04-07
Encoder Feedback Option Card
PG-X2
Table 3. GPD 515/G5, F7, and G7 Encoder Feedback Parameter List
Control
Method (2)
Digital Operator
Func
tion Group
Digital Operator
Disp
lay
Parameter Number
Parameter Name
Se
tting Ra
nge
Fa
c
tory
Se
tting
Cha
nge
During
Op
eratio
n
(1)
Data Selectio
n
V/f w/ PG
F
eed
b
ack
Flux
Ve
c
tor
ASR P Gain 1
C5-01
ASR
Proportional
Gain 1
0 to
300.00
0.00 O
O
O
ASR I Time 1
C5-02
ASR Integral
Time 1
0 to
10.000s
0.00s O
O
O
ASR P Time 2
C5-03
ASR
Proportional
Gain 2
0 to
300.00
0.00 O
O
O
ASR I Time 2
C5-04
ASR Integral
Time 2
0 to
10.000s
0.00s O
O
O
ASR Limit
C5-05
ASR Limit
0.0 to
20%
0.0% X
O
X
ASR Delay
Time
C5-06
ASR Primary
Delay Time
0.000 to
0.500s
0.000s X
X
O
ASR Gain SW
Freq
C5-07
ASR Switching
Frequency
0.0 to
400.00Hz
0.0Hz X
X
O
ASR
Tuning
ASR Integral
Limit
C5-08
ASR Integral
Limit
0 to
400%
400% X
X
O
(1) O = Yes, X = No.