2 communications connectors (cn2), 3 led indicators – Yaskawa VS-606V7 User Manual

Page 11

Advertising
background image

3 Component Names and Settings

11

3.2

Communications Connectors (CN2)

The communications connectors connect the SI-T/V7 Unit to the communications lines of
the MECHATROLINK-I or MECHATROLINK-II . The following table shows the pin num-
bers and their functions.

3.3

LED Indicators

The LED indicators indicate the status of the communications of the MECHATROLINK-I
or MECHATROLINK-II and the SI-T/V7 Unit.
However, these indicates are for maintenance checks at Yaskawa. Use the Digital Operator
to check the status.

Pin No.

Signal Name

I/O

Function

A1

(NC)

Not used.

A2

SRD

I/O

Send/receive data (-)

A3

SRD+

I/O

Send/receive data (+)

A4

(NC)

Not used.

B1

(NC)

Not used.

B2

SRD

I/O

Send/receive data (-)

B3

SRD+

I/O

Send/receive data (+)

B4

(NC)

Not used.

Shell

Shield

Not used.

Name

Display

Explanation

Color

Status

RUN

Green

Lit

Normal operation

Not lit

Communications CPU stopped, resetting hardware, RAM check
error, DPRAM check error, station address setting error, or
Inverter model code error

ERR

Red

Lit

Watchdog timeout error, communications error, or resetting hard-
ware

Red

Blinking

ROM check error (once), RAM check error (twice)*, DPRAM
check error (3 times)*, communications ASIC self-diagnosis error
(4 times) *, ASIC RAM check error (5 times), station address set-
ting error (6 times) *, Inverter model code error (7 times) *
*: Indicates the number of blinking.

Not lit

No communications error or self-diagnosis error

TX

Green

Lit

Sending data

Not lit

Sending of dara stopped, hardware reset

RX

Green

Lit

Searching for receiving carrier

Not lit

No receiving carrier found, resetting hardware

RUN TX

RX

ERR