2 mechatrolink communications cables, Wiring, Communications wiring example – Yaskawa VS-606V7 User Manual

Page 16: Important

Advertising
background image

16

4.2

MECHATROLINK Communications Cables

„

Wiring

Wire the MECHATROLINK communications cables to the communications connector
(CN2).

• For communications cables, use special shielded twisted-pair cables for MECHATROLINK com-

munications.
Recommended cable: JEPMC-W603-†† *

* †† is the length (m).

With USB male connector

• Install MECHATROLINK communications cables apart from main-circuit wiring and other elec-

trical and power lines.

• Connect the terminator (model No.: JEPMC-W6022) on the end of the communication lines.
• Maximum transmission distance is 50 m.
• Minimum wiring distance between stations is 0.5 m.

„

Communications Wiring Example

The following diagram is an example of communications wiring around the Inverters.

Fig. 3 Connection Diagram with VS-606V7 (3-phase, 200 VAC, 0.1kW)

IMPORTANT

NC

SRD-

D -

SRD+

SLD

MECHATROLINK

controller

Inverter

3-phase, 200 VAC,

0.1 kW

M

SI-T/V7

3-phase power supply

200 to 230 VAC

R

S
T

U
V

W

E

* If there are noise influences on communication,

remove the grounding cable.

SRD-

SRD+

NC

SLD

SRD-

SRD+

NC

SLD