Page 4 of 5 – Yaskawa iQpump1000 AC Drive User Manual

Page 4

Advertising
background image

Page 4 of 5

Yaskawa America, Inc., 2121 Norman Drive South, Waukegan, IL 60085, (800) YASKAWA (927-5292) Fax (847) 887-7310, [email protected], www.yaskawa.com, Document Number: TM.iQp1000.03 05/29/2014 © Yaskawa America, Inc.

Parameter

Jockey iQPump1000

P1 Setting

Booster iQPump1000

P2 and P3 Setting

Description

Comments

b5-02

Pressure

Tank

No Pressure

Tank

Pressure

Tank

No Pressure

Tank

Proportional Gain Setting (P)

Increase proportional gain to make iQpump1000 more responsive. Caution: can cause instability if value is too high.

2.0

4.0

2.0

4.0

b5-03

Pressure

Tank

No Pressure

Tank

Pressure

Tank

No Pressure

Tank

PI Integral Time (I)

Decrease integral time to make iQpump1000 more responsive. Caution: can cause instability if value is too low.

3.0 sec.

2.0 sec.

3.0 sec.

2.0 sec.

C1-01

9.0 sec.

9.0 sec.

Acceleration Time 1

Time it takes to accelerate the pump motor from zero to maximum speed.

C1-02

5.0 sec.

5.0 sec.

Deceleration Time 1

Time it takes to decelerate the pump motor from maximum speed to zero.

C6-02

Centrifugal

Pump

Submersible

Pump

Centrifugal

Pump

Submersible

Pump

Carrier Frequency

Note: Please refer to the iQPump1000 manual for drive full load amp de-ratings if setting C6-02 carrier frequency selection other than 6 or 7
for drives above 40HP.

2

7

2

7

E2-01

11

P2 = Mtr FLA, P3 = Mtr FLA Motor Rated Current

Set to the motor nameplate full load amps.

H1-07

73

73

Terminal S7 Input - Low City Pressure

Make sure Low City Switch is wired into S7-SN of all drives.

H5-01

1

P2 = 2, P3 = 3

Drive Node Address

P1-01

3

3

Pump Mode

Set drive software up for Memobus Multiplexing.

P1-03

XX PSI

XX PSI

Feedback Scaling

This should be the maximum range of the transducer output based on 4-20ma. If transducer is 200 PSI that this is what should be
programmed in P1-03.

P1-04

-5 PSI

-5 PSI

Start-Draw down Level

Note: Make sure to see the "-" negative sign on display.

P1-06

Centrifugal

Pump

Submersible

Pump

Centrifugal

Pump

Submersible

Pump

Minimum Pump speed

This should always be set based on where the pump curve starts working to overcome the head and system losses.

35.0 Hz

40.0 Hz

35.0 Hz

40.0 Hz

P1-11

XX PSI

XX PSI

High Feedback Level

High Pressure fault should be set on average 20 PSI over the system set point.

P1-12

4 sec.

4 sec.

High Feedback Level Delay Time

P4-10

1

1

AUTO Mode Operator Run Power Down Storage

This allows drive to recover and automatically run after a loss of Utility Power if run (Auto) command is via keypad.
Warning: System will automatically restart.

P4-12

Centrifugal

Pump

Submersible

Pump

Centrifugal

Pump

Submersible

Pump

Trust Bearing Frequency

Thrust bearing frequency shout not be disabled when using a submersible pump motor.

0.0 Hz

30.0 Hz

0.0 Hz

30.0 Hz

P4-21

1

1

Low City Input Select

Note: input is based on Normally Closed. (Open switch indicates low city pressure, and system will shut down)

P4-21

5 sec.

5 sec.

Low City On-Delay Time

P9-01

1

2

Lead Drive Select

Booster pumps will alternate every run cycle. Jokey pump does not alternate.

P9-02

2

2

Feedback Source

System programmed for redundant transducer feedback. Each drive has its own transducer.

P9-03

0 Hr.

0 Hr.

Alternation Time

Alternation disabled as the Jockey pump will always be the lead pump to start and the larger booster pumps will alternate every run cycle.

P9-05

2

0

Lag Fixed Mode

When the Jockey pump cannot keep up with the system demand a booster pump will stage on and the Jockey pump will turn off.

P9-06

59.5 Hz

59.5 Hz

Lag Fixed Speed

P9-08

2

2

Add Pump Mode

Sets the conditions for the lead pump drive so that the output speed must rise above P9-09 and the pressure to fall below P9-10
before adding an additional pump to the system.

P9-09

59.5 Hz

59.5 Hz

Add Freq Level

Sets the system to stage on lag pump when lead pump is above P9-09 level and the system is 5PSI below Auto Set point.

P9-10

5.0 PSI

5.0 PSI

Add Delta Level

Sets the system to stage on lag pump when lead pump is above P9-09 level and the system is 5PSI below Auto Set point.

P9-11

14 sec.

14 sec.

Add Delay Time

Sets the time when the lag pump will stage on. Adjust as needed for system operation.

P9-12

0

0

Remove Pump Mode

P9-13

45.0 Hz

45.0 Hz

Remove Frequency Level

Sets the lag pump output frequency when it de-stages and goes back to a single lead pump. May have to adjust based on pump system
curve.

P9-15

5 sec

5 sec

Remove Delay Time

Sets the time when the lag pump will de-stage when speed falls below P9-13.

P9-18

98.0%

98.0%

High Feedback Quick De-stage

Allows program to this value when using High Pressure as Fault.

P9-20

2

0

Allow Network Run

Jockey Pump will be the first to run at all times until a booster pump is staged on.

P9-21

7

8

Run Priority

P9-24

0

5 sec

Lead swap at speed

When the booster pumps shuts down or goes into sleep mode for 5 seconds the lead is handed back to the Jockey pump .

P9-25

2 for Duplex, 3 for Triplex

2 for Duplex, 3 for Triplex

Max Number of Running Pumps

Program network for 2 or 3 pumps on the system.

Q1-01

120 PSI

120 PSI

System Setpoint

Note: Program this value last on the main keypad screen using Q1-01. U1-01 auto set point is the same as Q1-01.

Step

8

Parameter setup for triplex system with jockey pump and two pumps as boosters with or without pressure tank.
Transducers used with a range of 200 PSI and System setpoint set for 120 PSI. Booster pumps will lead-lag with 24hrs alternation.

iQpump1000 AC Drive
Multiplex Quick Start Procedure

Advertising