Controller installation, Installing the controller cabinet, Connecting the valve control wiring – Irritrol Rain Dial R User Manual

Page 5: 32 1 mv, Eng lish

Advertising
background image

5

Controller Installation

Installing the Controller Cabinet

Select a sheltered location for the indoor model Rain Dial-R such as a garage or service room,

preferably within 5’ (1.5m) of a grounded electrical outlet. For outdoor controllers, choose a location

that protects against direct exposure to sun and contact with irrigation spray, and is at least 5’ (1.5m)

away from any motorized equipment.
1. Drive the provided stainless steel screw into a wall stud at a eye-level, leaving 1/4” (6.4mm) of

the screw shaft exposed.
Note: Use screw anchors when installing on drywall or masonry.

2. Hang the controller on the screw using the keyhole-shaped slot.
3. To secure the controller, drive one or two screws through the lower mounting holes.

Note: The lower mounting holes in the Outdoor cabinet have a thin veneer that is easily pierced

when installing the mounting screw during installation.

Connecting the Valve Control Wiring

For best results, use connection wire cable specifically designed for direct burial for automatic irrigation

systems. Use 18-AWG wire for connections up to 800’ from the controller, or heavier 14-AWG (2.0mm2 )

wire for connections up to 2000’. A separate wire for each valve (and relay) connection and at least one

common (return) wire is required.
Note: If control wire conduit is required, install it at this time. For conduit installation, use the 3/4”

(19mm) access hole in the indoor cabinet, or the threaded 1.25” NPT opening in the outdoor cabinet.
1. Route the control wire from the controller location to the valve(s).
2. Attach a separate control wire to either lead of each valve solenoid.
3. To provide a common (return) wire, attach the remaining lead of each valve solenoid to a single wire.

Note: To prevent corrosion and a possible short circuit, use waterproof wire connectors on all

external wire splices.
For reference at the controller, note the wire color used for each valve connection and its

corresponding watering zone.

4. Route the cable through the

largest opening in the base of

the controller cabinet or through

conduit if installed. Remove the

cable jacket to expose about 8”

of wires. Carefully remove 3/8” of

insulation from the end of each

wire to be connected.

5. Secure each valve wire to

numbered terminal in the

preferred operating sequence

order.

6. Connect the common wire to the

terminal labeled “VC.”

7. If applicable, connect one leg

of the master valve or pump

start relay control wire to the

terminal labeled “MV/PUMP”, and

the remaining leg to the valve

common wire.
Note: The controller does not

supply power to operate a pump.

The pump start relay must have

a nominal coil voltage of 24 VAC,

rated at 0.375A maximum.

EARTH

GROUND

MV/

Pump

Sensor

+

-

7

8

9 10 11 12

1

2

3

4

5

6

24 VAC

VC

Sprinkler

Control Valves

Common Wire

Pump Start Relay

or Master Valve

24V Relay

Master Valve/Pump Terminal

Valve Common Terminal

3

2

1

MV

Eng

lish

Advertising