Eaton Electrical SPI9000 User Manual

Page 16

Advertising
background image

SPI9000 Inverter Unit FI9 – FI14 User Manual

1-6

For more information visit: www.EatonElectrical.com

MN04004002E

September 2006

Table 1-4: Technical Information

Description

Specification

Supply Connection

Input Voltage V

in

465 – 800V DC; 380 – 500V AC (-0%. to +0%)
640 – 1100V DC; 525 – 690V AC (-0% to +0%)
The waviness of the inverter supply voltage, which is formed in
rectification of the electric network’s alternating voltage in basic
frequency, must be less than 50V peak-to-peak.

Input Current I

in

(sqrt3 x U

mot

x I

mot

x cosϕ) / (V

in

x 0.98)

DC Bank Capacitance

FI9 380 – 500V: 4950 μF; FI9 525 – 690V: 3733 μF
FI10 380 – 500V: 9900 μF; FI10 525 – 690V: 7467 μF
FI12 380 – 500V: 19800 μF; FI12 525 – 690V: 14933 μF
FI13 380 – 500V: 29700 μF; FI13 525 – 690V: 22400 μF

Starting Delay

5 seconds (FI9 and greater)

Motor Connection

Output Voltage

3 ~ 0 – V

in

/ 1.4

Continuous Output Current

I

H

: Ambient temperature max. +50°C,

overload 1.5 x I

H

(1 min./10 min.)

I

L

: Ambient temperature max. +40°C,

overload 1.1 x I

L

(1 min./10 min.)

Starting Torque

I

S

for two seconds (torque motor dependent)

Peak Current

I

S

for 2 seconds every 20 seconds

Output Frequency

0 – 320 Hz; 7200 Hz (special)

Frequency Resolution

Application dependent

Control Characteristics

Control Method

Frequency control V/f
Open loop: Sensorless vector control
Closed loop: Frequency control
Closed loop: Vector control

Switching Frequency
(See Parameter 2.6.9)

380 – 500V, 1 – 10 kHz; Factory default 3.6 kHz
525 – 690V, 1 – 6 kHz; Factory default 1.5 kHz

Frequency Reference
Analog Input
Panel Reference

Resolution 0.1% (10 bits); Accuracy ±1%
Resolution 0.01 Hz

Field Weakening Point

30 – 320 Hz

Acceleration Time

0 – 3000 sec

Deceleration Time

0 – 3000 sec

Braking Torque

DC brake: 30% * T

N

(without brake)

Ambient Conditions

Ambient Operating Temperature -10°C (no frost) to +40°C: I

H

-10°C (no frost) to +40°C: I

L

Storage Temperature

-40 to 158°F (-40 to 70°C)

Relative Humidity

0 – 95% RH, non-condensing, non-corrosive,
no dripping water

Air Quality:
– Chemical Vapors
– Mechanical Particles

IEC 721-3-3, unit in operation, Class 3C2
IEC 721-3-3, unit in operation, Class 3S2

Altitude

100% load capacity (no derating) up to 1,000m
1% derating for each 100m above 1000 (maximum, 3000m)

Advertising