Eaton Electrical SPI9000 User Manual

Page 62

Advertising
background image

SPI9000 Inverter Unit FI9 – FI14 User Manual

5-10

For more information visit: www.EatonElectrical.com

MN04004002E

September 2006

If you are in some other menu than menu M3 and try to start the motor by pressing the
START button when the keypad is not selected as the active control place, you will get an
error message: Keypad Control NOT ACTIVE.

Selection of Control Place

There are three different places (sources) where the inverter can be controlled. For each
control place, a different symbol will appear on the alphanumeric display:

I/O terminals

Keypad (panel)

Fieldbus

You can change the control place by entering the edit mode with Menu Button Right. The
options can then be browsed with the Browser buttons. Select the desired control place with
the ENTER button. See Figure 5-7.

Figure 5-7: Selection of Control Place

Keypad Reference

The keypad reference submenu (P3.2) displays and allows the operator to edit the frequency
reference. The changes will take place immediately. This reference value will not, however,
influence the rotation speed of the motor unless the keypad has been selected as the active
control place.

Note: The maximum difference in RUN mode between the output frequency and the keypad

reference is 6 Hz. The program automatically monitors the keypad reference value.

You may edit the reference value (pressing the ENTER button is not necessary).

Control Place

I/O Remote

Keypad control

M3

P1

P4

Control Place

I/O Remote

Control Place

Keypad

Control Place

Keypad

Advertising