SPI9000 Inverter Unit FI9 – FI14 User Manual

MN04004002E

For more information visit: www.EatonElectrical.com

5-25

September 2006

Hardware Settings

Note: The Hardware settings submenu is protected with a password. Store the password in a

safe place!

In the Hardware Settings submenu (S6.7) under the System menu, you can further control
some functions of the hardware in your inverter. The functions available in this menu are
Internal brake resistor connection, Fan control, HMI acknowledge timeout and HMI retry.

Internal Brake Resistor Connection (P6.7.1)

This function tells the inverter, whether the internal brake resistor is connected or not. If you
have ordered the inverter with an internal brake resistor, the default value of this parameter is
Connected. However, if it is necessary to increase braking capacity by installing an external
brake resistor, or if the internal brake resistor is disconnected for another reason, it is
advisable to change the value of this function to Not conn. in order to avoid unnecessary
fault trips.

Enter the edit mode by pressing Menu Button Right. You can change the brake resistor
information with the Browser buttons. Confirm the change with the ENTER button or return
to the previous level with Menu Button Left.

Note: The brake resistor is available as optional equipment for all classes. It can be installed

internally in classes FR4 to FR6.

Figure 5-23: Internal Brake Resistor Connection

InternBrakeRes

P6.7.

HW Settings

System Menu

M6

S1

S8

P1

P4

Connected

InternBrakeRes

Not conn.

Connected

56.7

P6.7.

P6.7.

InternBrakeRes