SPI9000 Inverter Unit FI9 – FI14 User Manual

MN04004002E

For more information visit: www.EatonElectrical.com

6-3

September 2006

●

Check in Monitoring Menu M1 that the value of Output Frequency changes
according to the change of frequency reference.

●

Press the STOP button on the keypad.

9. Perform the start-up tests without the motor being connected to the process. If this is

not possible, make sure that each test can be done safely prior to performing it. Inform
your co-workers of the tests.

●

Switch off the DC supply voltage and wait until the drive has stopped as advised on
Page 6-1, Safety Precautions.

●

Connect the motor cable to the motor and to the motor cable terminals of the
inverter.

●

Make sure that all Start/Stop switches are in Stop positions.

●

Switch the supply voltage ON.

●

Repeat Test A or B in step 8.

10. Connect the motor to the process (if the start-up test was performed without the motor

being connected). Inform our co-workers of the tests.

●

Before running the tests, make sure that this can be done safely.

●

Repeat Test A or B in step 8.