Energy Tech Laboratories New Yorker CL Series User Manual

Page 7

Advertising
background image

7

Figure 2: Minimum Installation Clearances To Combustible Materials (Inches)

TABLE 2: RATING DATA

NOTE 1: Listed clearances comply with American National
Standard NFPA 31, Standard for the Installation of Oil Burn-
ing Equipment.

NOTE 2: CL Series boilers can be installed in rooms with
clearances from combustible material as listed above. Listed
clearances cannot be reduced for alcove or closet installa-
tions.

NOTE 3: For reduced clearances to combustible material,
protection must be provided as described in the ANSI/NFPA
31 standard.

C

A

Above

B

Front

Chimney

Connector

D

Rear

E

Sides

6

24

18

6

6

Boiler Model

No. *

Burner

Capacity

DOE Heating

Capacity

I=B=R NET Ratings

Minimum Chimney

Requirements

AFUE %

GPH

MBH

Water

MBH

Steam

MBH

Water

MBH

Steam

MBH

Steam

Sq. Ft.

Round

In. Dia.

Rectangle

In. x In.

Height

Ft.

Water Steam

CL3-091(W)

0.65

91

80

---

70

---

---

6

8 x 8

15

86.0

---

CL3-091(S)

0.65

91

---

78

---

56

233

6

8 x 8

15

---

84.1

CL3-105(W)

0.75

105

91

---

79

---

---

6

8 x 8

15

85.1

---

CL3-105(S)

0.75

105

---

90

---

68

283

6

8 x 8

15

---

83.8

CL3-140(W)

1.00

140

120

---

104

---

---

6

8 x 8

15

83.6

---

CL3-140(S)

1.00

140

---

119

---

89

370

6

8 x 8

15

---

82.7

CL4-126(W)

0.90

126

111

---

97

---

---

7

8 x 8

15

85.8

---

CL4-126(S)

0.90

126

---

108

---

81

338

7

8 x 8

15

---

84.1

CL4-175(W)

1.25

175

152

---

132

---

---

7

8 x 8

15

84.2

---

CL4-175(S)

1.25

175

---

149

---

112

467

7

8 x 8

15

---

83.5

CL4-210(W)

1.50

210

179

---

156

---

---

7

8 x 8

15

83.1

---

CL4-210(S)

1.50

210

---

177

---

133

554

7

8 x 8

15

---

82.6

CL5-168(W)

1.20

168

147

---

128

---

---

8

8 x 8

15

85.7

---

CL5-168(S)

1.20

168

---

144

---

108

450

8

8 x 8

15

---

83.7

CL5-245(W)

1.75

245

210

---

183

---

---

8

8 x 8

15

83.0

---

CL5-245(S)

1.75

245

---

207

---

155

646

8

8 x 8

15

---

82.5

CL5-280(W)

2.00

280

238

---

207

---

---

8

8 x 8

15

82.5

---

CL5-280(S)

2.00

280

---

235

---

176

733

8

8 x 8

15

---

82.3

* Boiler Model Suffix: (W) = Water, (S) = Steam