II. Installation Instructions

A.

REMOVE CRATE

1. Remove all fasteners at crate skid.

2. Lift outside container and remove all other

inside protective spacers and bracing. Remove
miscellaneous steam or water trim carton.

3. Using hand truck or pipe rollers under skid, move

boiler into position along side installation site.

B.

REMOVAL OF BOILER FROM SKID

1. Boiler is secured to base with 4 carriage bolts, 2 on

left side and 2 on right side. See Figure 3. Remove
all bolts.

1. PACKAGED CL™ Series boilers are shipped with

the highest input oil nozzle installed in the burner.

Oil nozzles for lower firing rates are shipped
loose for the CL3 through CL5 models, attached
to the burner. Select the proper oil nozzle for the
installation. The lower input nozzle will provide

greater boiler efficiency. However, boiler output

will be reduced. Refer to Table 2 for firing rates.
If the higher rate is desired, inspect the installed
nozzle and assure that the nozzle is the correct size

and type as specified in Tables 9 and 9A of this
manual.

If a lower input is desired, remove the nozzle

which was factory installed. Locate the lower firing

rate nozzle that is supplied loose. Confirm the

nozzle is the proper size and type for the lower firing

rate as specified in Tables 9 and 9A of this manual.
Install the proper nozzle in the burner nozzle
adaptor.

2. On the Beckett AFG Burner, use the following

procedure to complete the inspection, check the settings

and to change the nozzle to a lower firing rate:

a. Loosen two (2) igniter latching screws, rotate

tabs and swing open igniter about hinge.

b. Loosen knurled nut and disconnect copper

connector tube.

c. Remove nozzle line electrode assembly.

d.

If high firing rate is desired, confirm the nozzle
is the proper size and type, refer to Table 9, then
proceed to Item i. below.

e. If a lower input is desired, remove the nozzle

that was factory installed.

f. Remove Beckett MD(V1) or MB(L1) head.

g. Locate the desired nozzle. Refer to Table 9 for

proper nozzle. The nozzle must be securely
installed to assure leak free joints between the
nozzle and adapter. When installing the nozzle,
be careful not to bump or move the burner
electrodes.

NOTE: On the CL3-091 (0.65 GPH) burner

application, a low firing rate baffle is required.

Baffle is shipped loose with nozzles. Install

baffle per Beckett Instruction included with

baffle.

h. Reinstall Beckett MD(V1) or MB(L1) Head.

i. Inspect and measure burner electrodes. Refer

to Figure 25 for the proper electrode setting.
Readjust electrode setting to the proper
dimensions if necessary. Refer to Figure 25.

j. Reinstall nozzle line electrode assembly.

k. Connect copper connector tube.

2. Tilt boiler to right and to rear. Using right rear leg

as pivot, rotate boiler 90° in a clockwise direction,

and lower left side of boiler to floor. Tilt boiler
and remove crate skid. Care should be exercised to
prevent damage to jacket or burner.

C.

MOVE BOILER TO PERMANENT POSITION by

sliding or walking.

D.

INSPECT COMBUSTION TARGET WALL AND

COMBUSTION CHAMBER LINER

1. OPEN FLAME OBSERVATION DOOR AND/

OR BURNER SWING DOOR on front of boiler.

Use flashlight to inspect target wall secured to
rear section with silastic sealant. Inspect ceramic

fiber blanket secured to floor of boiler with water
glass adhesive. If either is damaged they must be
replaced.

E.

INSPECT NOZZLE, ELECTRODES INSERTION
DEPTH AND TURBULATOR SETTING/CHANGE
FIRING RATE: Refer also to Model F3 & F5
Installation Manual, Riello 40 Series Residential Oil
Burners
(C6501010) or Model F10 Installation Manual,
Riello 40 Series Residential Oil Burners
(2902554).

Figure : Removal of Boiler From Skid