Precision Digital PD562 User Manual

Page 33

Advertising
background image

To prevent electric shock, be sure to turn off power to the Nova Controller and the source circuit breaker
before wiring.

7.8 Retransmission Output Connection.(RET)

„ Be sure to connect to correct polarities. Connecting to a wrong polarity may cause a controller malfunction.
„ Use shielded wires for the wiring and connect independently to ground (1 point grounding).

To prevent electric shock, be sure to turn off power to the Nova Controller and the source circuit breaker
before wiring.

!

CAUTION

!

CAUTION

Retransmitting Output (RET)

-

+

RET+

NOVA

SHIELD

RET-

Receiver

(Recorder, etc)

To prevent electric shock, be sure to turn off power to the Nova Controller and the source circuit breaker
before wiring.

!

CAUTION

7.9 Relay Output Connection (RELAY)

!

CAUTION

COM

NOVA

Relay: NC - Normally Closed Connection

Relay: NO - Normally Open Connection

4 to 20 mADC, 600

Ω max

or 14-18 VDC @ 20 mA max

PD560 Series Nova Digital Process and Temperature Meter

Instruction Manual

33

Advertising
This manual is related to the following products: