Relay Outputs
RATINGS

Alarm1: 250 VAC @ 3 A or 30 VDC @ 3 A (resisitive load)
Alarm2, 3: 250 VAC @ 1 A or 30 VDC @ 1 A (resistive load)

ELECTRICAL NOISE

A suppressor (snubber) should be connected to each

SUPPRESSION

relay contact switching inductive loads, to prevent
disruption to the microprocessor's operation.
Recommended suppressor value: 0.1

μF/470 Ω,

250 VAC (PDX6901)

DEADBAND

For alarm operations, 0-100% of full scale, user selectable

HIGH OR LOW

User may program each relay for high or low trip point

ALARM

TIME DELAY

0 to 99 minutes 59 seconds alarm trip delay for each alarm

FAIL-SAFE

Programmable

OPERATION

Independent for each alarm relay

AUTO INITIALIZATION When power is applied to the meter, alarm relays will

reflect the state of the input to the meter except standby
alarms.

Digital Inputs

CONFIGURATION

Two contacts, two operating modes

CONTACTS

Normally open switches (external excitation note required)
or open collector transistor

OPEN CIRCUIT

Approximately 5 VDC

VOLTAGE

LOGIC LEVELS

LO = 0 to 0.8 VDC, HI = 4.7 to 28 VDC

OPERATION MODES

Mode 1: Record and reset maximum and minimum display
values simultaneously. Mode 2: Record and reset maximum
and minimum display values independently.

Serial Communications

PROTOCOLS

Modbus (ASCII, RTU), PC software

UNIT ADDRESS

1 to 99 (Max 31 units connected)

BAUD RATE

600, 1200, 2400, 4800, 9600, 19200 bps, user selectable

RESPONSE TIME

0 to 100 ms delay response time
10 ms increments user selectable

DATA

7 or 8 bit user selectable

PARITY

None, even, or odd

Approvals

UL RECOGNIZED

USA and Canada
Process Control Equipment

UL FILE NUMBER

E244207

CE COMPLIANT