10 use of an external relay – Precision Digital PD570 User Manual

Page 38

Advertising
background image

If the load inductance is over the controller specifications, the output may need a RC filter (snubber) or
diode to properly handle frequent relay switching operations.

7.10 Use of an External Relay

!

CAUTION

External AC

Power

External DC

power

(1) DC External Relay

(2) AC External Relay

CR Filter (snubber)
(Connect directly to the relay coil terminals)

Controller

R

!

CAUTION

!

CAUTION

R

Relay
(Verify relay coil ratings are less than the voltage and current ratings of the relay
contacts of the controller)

Diode
(Connect directly to the relay coil terminals)

Controller

!

CAUTION

!

CAUTION

Relay
(Verify relay coil ratings are less than the voltage and current ratings of the relay
contacts of the controller)

Switching Inductive Loads

When using switching in ductive loads, the use of RC networks (snubbers) for AC loads or diodes for DC loads is
recommended to prevent disrupting the microprocessor's operation. The suppressors also prolong the life of the
relay contacts. Suppression can be obtained with resistor-capacitor (RC) networks or diodes assembled by the
user or purchased as complete assemblies.
For AC loads, choose R and C as follows:
R: 0.5 to 1

Ω for each volt across the contact

C: 0.5 to 1

μF for each amp through closed contacts

Notes:
1. Use capacitors rated for 250 VAC.
2. RC networks may affect load release time of solenoid loads. Check to confirm proper operation.
3. RC networks are available from Precision Digital and should be applied to each relay contact switching an

inductive load. Part number: PDX6901.